Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM05023

Parcel: 110061550

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/02/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*OK ELECTRICAL FINAL
11/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245$ INSTALL GFI LABEL ON DUPLEX OUTLETS ON LOAD SIDE OF GFI'S.
EXTERIOR OUTLETS NEED IN USE COVERS
DISPOSAL CORD'S TO BE 18' TO 36"
INSTALL HOLD DOWNS ON BACKFED MAIN BREAKERS
LABEL PANEL DIRECTORY'S CORRECTLY & LEDGEBLY
INSTALL BLANK COVERS ON ALL UNUSED
OUTLETS AND LIGHTS IN GARAGE.
NOTE: I WOULD LIKE TO CHECK THIS HOT IF POSSIBLE
MAKE SURE DEAD FRONT FIT CORRECTLY IN PANELS AND BLANK OFF OPEN KO'S
PROVIDE ACCESS TO ROOF.