Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*15 PSI TEST IS OK CIRCUIT BREAKER & GAS CONNECTION OK AS PER MY CONVERSATION WITH JASON. |
|
| 10/05/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 3/8" ID GAS FLEX IS NOT ADEQUATE FOR 120,000 BTU FURNACE. PROVIDE A MIN 10 LBS PRESSURE TEST ON ALL NEW GAS PIPING. NEED TO SEE CONNECTION INSIDE HOUSE. HORIZONTAL SECTION OF CONDENSATE DRAIN HAS NO SLOPE. NEED TO SEE ELECTRICAL CIRCUIT PANEL & BREAKER. RECALL FOR INSPECTION |