Permit: T05CM05021

Parcel: 134170070


Addresses:

7409 E 18TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/19/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*15 PSI TEST IS OK
CIRCUIT BREAKER & GAS CONNECTION OK AS PER MY CONVERSATION WITH JASON.
10/05/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 3/8" ID GAS FLEX IS NOT ADEQUATE FOR 120,000 BTU FURNACE. PROVIDE A MIN 10 LBS PRESSURE TEST ON ALL NEW GAS PIPING. NEED TO SEE CONNECTION INSIDE HOUSE.
HORIZONTAL SECTION OF CONDENSATE DRAIN HAS NO SLOPE.
NEED TO SEE ELECTRICAL CIRCUIT PANEL & BREAKER. RECALL FOR INSPECTION