Permit: T05CM04996

Parcel: 107081270


Addresses:

747 W TIPTON DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/09/2012 FRAMING Approved IVRS - Inspection :*
10/02/2012 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE CORRECT NAIL PLATE PROTECTION FOR CSST GAS PIPING
2) PROVIDE TRUSS DESIGN DRAWINGS
3) FIRE STOP ALL CHASES
4) PROVIDE 36" LANDING AND MAP 7 3/4" RISE MIN 10" RIM AT STAIRS, AND FIRE STOP STAIRS
5) PROVIDE SOFFIT FOR HVAC DUCTS
6) CRIPPLE ALL DUCT
7) PROVIDE CLEARANCE AT B-VENT