Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04991

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/28/2006 ELECTRIC - FINAL Approved
08/25/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. REMOVE PAINT AND TIGHTEN SPLIT BOLT FOR BONDING CONDUCTOR @ SERVICE.
2. PROVIDE PROPER ENTRY/FRONT WORKING CLEARANCE FOR AC DISCONNECT (LOWER ROOF)
3. IDENTIFY ALL RTU'S ON ROOF AS TO WHAT UNIT THEY ARE
4. TIGHTEN ALL BOND SCREWS IN RTU'S DISCONNECTS
5. LOWER ROOF GFI NOT WORKING
6. WIRING/LOADS NOT PER PLAN - PANEL ORIGINATION
7. PANEL DIRECTORY'S NOT IDENTIFIED
8. SAFE OFF EXTERIOR LIGHTING AT DRIVE THROUGH NOT INSTALLED

PARTIAL INSPECTION WILL CHECK RACEWAYS/BOND CLAMP NEXT INSPECTION.
08/21/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK OUTDOOR LIGHTING
08/15/2006 ELECTRIC - FINAL Partial Approval
07/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
CALL FOR FINAL WHEN SERVICE IS ENERGIZED.