Permit: T05CM04991

Parcel: 12409156A


Addresses:

1821 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/28/2006 ELECTRIC - INTERMEDIATE Approved
07/31/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/28/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
POWER WAS APPROVED AND TEP NOTIFIED ON 6/27/06
06/26/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/23/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. BOND NEUTRAL TO DISCONNECT ENCLOSURE -
NEC 250.24(B)
2. BOND CT ENCLOSURE - NEC 250.90
3. IDENTIFY SERVICE DISCONNECT - NEC 230.70
4. BOND WIRE FOR SERVICE NIPPLE UNDER SIZED - NEC 250.92
5. INSTALL ADDRESS
6. BOND SERVICE RISER - NEC 250.90
7. BOND METER ENCLOSURE AND RACEWAY -- NEC 250.90
8. TERMINATE FEEDERS INSIDE
06/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER SECONDARY'S & POLE BASES
06/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER IN INTERIOR AFTER CORRECTIONS MADE.
1. TIGHTEN ALL SET SCREWS ON RACEWAYS.
04/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER INTERIOR ELECTRICAL UNDERGROUND.