Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM04991
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
07/31/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/28/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* POWER WAS APPROVED AND TEP NOTIFIED ON 6/27/06 |
|
06/26/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/23/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND NEUTRAL TO DISCONNECT ENCLOSURE - NEC 250.24(B) 2. BOND CT ENCLOSURE - NEC 250.90 3. IDENTIFY SERVICE DISCONNECT - NEC 230.70 4. BOND WIRE FOR SERVICE NIPPLE UNDER SIZED - NEC 250.92 5. INSTALL ADDRESS 6. BOND SERVICE RISER - NEC 250.90 7. BOND METER ENCLOSURE AND RACEWAY -- NEC 250.90 8. TERMINATE FEEDERS INSIDE |
|
06/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER SECONDARY'S & POLE BASES |
|
06/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER IN INTERIOR AFTER CORRECTIONS MADE. 1. TIGHTEN ALL SET SCREWS ON RACEWAYS. |
|
04/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER INTERIOR ELECTRICAL UNDERGROUND. |