Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECTLY IDENTIFY ALL PANEL DIRECTORY'S NEC 408.4 2. ALL CONDUCTORS #4 AND LARGER NEED BUSHING NEC 300.4 (F) 3. TIGHTEN ALL FITTINGS ON SEAL TIGHT -- NEC 110 4. PROPERLY REPAIR ALL DAMAGED INSULATION ON CONDUCTORS THAT DID NOT HAVE A BUSHING FOR PROTECTION NEC 110, 310, 300 5. BOND ELECTRODE TO LIGHT POLE. |
|
| 06/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SERVICE GFI TEST REPORT PROVIDED |