Permit: T05CM04987

Parcel: 22502008C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/21/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CORRECTLY IDENTIFY ALL PANEL DIRECTORY'S NEC 408.4
2. ALL CONDUCTORS #4 AND LARGER NEED BUSHING
NEC 300.4 (F)
3. TIGHTEN ALL FITTINGS ON SEAL TIGHT -- NEC 110
4. PROPERLY REPAIR ALL DAMAGED INSULATION ON CONDUCTORS THAT DID NOT HAVE A BUSHING FOR PROTECTION NEC 110, 310, 300
5. BOND ELECTRODE TO LIGHT POLE.
06/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SERVICE GFI TEST REPORT PROVIDED