Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PROVIDE TEST REPORT. |
|
| 06/01/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* SERVICE INSPECTION ONLY KEVIN 909-4795 1. SERVICE CONDUCTOR RACEWAYS NEED TO BE BONDED NEC 250.92 (A) & (B) 2. SERVICE GUTTER NEEDS TO BE BONDED NEC 250.92 (A) (B) 3. SIZE RACEWAY/GUTTER BONDING JUMPER CORRECTLY NEC 250.102 (C) 4. SIZE BONDING CONDUCTOR TO CT ENCLOSURE CORRECTLY NEC 250.102 (C) 5. SERVICE NEEDS TO CONFORM WITH NEC 230.95 BEFORE IT CAN BE ENERGIZED. |