Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
06/07/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PROVIDE TEST REPORT.
06/01/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*
SERVICE INSPECTION ONLY
KEVIN 909-4795
1. SERVICE CONDUCTOR RACEWAYS NEED TO BE BONDED
NEC 250.92 (A) & (B)
2. SERVICE GUTTER NEEDS TO BE BONDED NEC 250.92 (A) (B)
3. SIZE RACEWAY/GUTTER BONDING JUMPER CORRECTLY
NEC 250.102 (C)
4. SIZE BONDING CONDUCTOR TO CT ENCLOSURE CORRECTLY NEC 250.102 (C)
5. SERVICE NEEDS TO CONFORM WITH NEC 230.95
BEFORE IT CAN BE ENERGIZED.