Permit: T05CM04982

Parcel: 13323190A


Addresses:

7810 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/12/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES.
05/10/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
STRAP FLEX DUCT EVERY 5'
PLANS REQUIRE 24 GA. HANGER STRAP W/CRADLES. REMOVE DIPS & SAGS.
BE SURE DUCT SMOKE DETECTORS HAVE REMOTE AUDIBLE & VISIBLE ALARMS.
SECURE DUCT & INSULATION AT START COLLARS BETTER.
04/12/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT OK TO PROCEED.
CONDENSATE DRAINS OK
PROVIDE BACKING AROUND CEILING BOXES IN RESTROOMS AS DISCUSSED WITH INSTALLER.