Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T05CM04982
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES. |
|
05/10/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* STRAP FLEX DUCT EVERY 5' PLANS REQUIRE 24 GA. HANGER STRAP W/CRADLES. REMOVE DIPS & SAGS. BE SURE DUCT SMOKE DETECTORS HAVE REMOTE AUDIBLE & VISIBLE ALARMS. SECURE DUCT & INSULATION AT START COLLARS BETTER. |
|
04/12/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED. CONDENSATE DRAINS OK PROVIDE BACKING AROUND CEILING BOXES IN RESTROOMS AS DISCUSSED WITH INSTALLER. |