Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2006 | ELECTRIC - UFER | Approved | IVRS - Inspection :*OK ?? TO REBAR THRU PVC CONDUIT | |
| 01/10/2006 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* 1. BOND TO BE TO 20" SECTION OF REBAR AT BOTTOM OF FOOTING 2. RACEWAY IF METAL TO BE INSTALLED PER 250.64 |