Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T05CM04963
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2007 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
04/04/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. INSPECTION HOLES FOR 10' LIFT APPROVED RECALL AFTER GROUT |
|
04/03/2007 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 4' MAX GROUT LIFT FIRST FOUR FEET NEVER GROUTED 2. PROVIDE INSPECTION PORTS FOR 10' LIFT |
|
03/27/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) FIRST LIFT APPROVED |