Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM04961
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
10/14/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) OK TO COVER ALL AREAS 2) CORRECTIONS MADE OK 3) PLAN CALLS FOR HAIR TRAP AT NEW SHAMPOO BOWL |
|
10/12/2005 | PLUMBING - FINAL | Not ready for Inspection | NOT INSTALLED PER PLAN-NO VENT FRO SHAMPOO BOWL USE DRAINAGE FITTINGS SLOPE AT 2 PER CENT FURNCO COUPLINGS NOT PERMITTED IN THE WALL . HOT LINE TO BE INSULATED. INSPECTION STOPPED |