Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/17/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* HAVE CITY APPROVED PLAN ON SITE 1. PROVIDE DETAIL PLAN OF INTERCONNECTION OF POTABLE WATER SYSTEM WITH POSSIBLE CONTAMINANTS & POLLUTANTS TO PROVIDE CORRECT BACKFLOW PROTECTION OF POTABLE WATER SYSTEM ON THIS SITE. 2. SEE NOTE #13 PLUMBING GENERAL NOTES. 3. HOSE BIBS REQUIRE VACUUM BREAKERS, THIS IS NOT CORRECT PROTECTION OF POTABLE WATER SYSTEM FROM CROSS CONNECTION WITH CHEMICALS ON THIS SITE. 4. PROVIDE REVISED, APPROVED PLAN OF ADDITIONAL PIPING THAT IS INSTALLED. |
|
| 10/13/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. WATER HEATER T&P RUN TO DAYLIGHT. 2. SUPPORT EXPANSION TANK. 3. LIST MAY NOT BE COMPLETE. |