Permit: T05CM04931

Parcel: 141114100


Addresses:

7850 S RITA RD


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T05CM04931

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2006 ELECTRIC - UFER Approved IVRS - Inspection :*
09/01/2006 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
RODS 5' APART
NEED 6' PER NEC 250
07/28/2006 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
OK 1 - 1" TELEPHONE FEED
OK 3 - PAR. 3" PVC SCH. 40 W/RIDGID 90'S
OK 3 - 1" AT CAR WASH
OK 1 1/2 - DRYER SENSOR
OK 3/4" - CONDUIT @ VACUUMS