Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2006 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 09/01/2006 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* RODS 5' APART NEED 6' PER NEC 250 |
|
| 07/28/2006 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* OK 1 - 1" TELEPHONE FEED OK 3 - PAR. 3" PVC SCH. 40 W/RIDGID 90'S OK 3 - 1" AT CAR WASH OK 1 1/2 - DRYER SENSOR OK 3/4" - CONDUIT @ VACUUMS |