Permit: T05CM04922

Parcel: 140260550

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM04922

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
05/03/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
AS ALWAYS YOU NEED TO READ THE NOTES FROM THE PREVIOUS INSPECTIONS.
- ALSO CALL FOR AND HAVE APPROVED ALL REQURED INSPECTIONS BEFORE CALLING FOR FINAL.
- REMOVE WC IN MASTER BATH (EAST WALL) BECAUSE THE CLOSET FLANGE WAS NOT INSPECTED.
- INSTALL THE RIGHT CLOSET FLANGE AND SECURE RING TO FLOOR AS REQUIRED BY THE UPC INSTALLATION STANDARDS.
- UNCOVER BACKWATER VALVE OR PIPING IF IT WAS REMOVED.
- IT DOES NOT APPEAR THAT A BW VALVE IS NECESSARY.
- EXPOSE YARD WATER CONNECTION AT BUILDING.
- PROVIDE PLAN SHOWING ACCEPTANCE OF AAV.