Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM04922

Parcel: 140260550

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM04922

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*13 PSI TEST FROM METER TO WATER HEATER, FROM METER TO WATER HEATER, FURNACE STOVE OK
PROVIDE BONDING OF BUILDING GAS PIPING
01/26/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
9.3 - PSI PRESSURE DROP TO 7.8
CHECK FOR LEAKS
USE OF APPROVED PIPE CLAMPS REQUIRED
1 1/2 TRAP ARM MAX 42"