Permit: T05CM04911

Parcel: 11713038C


Addresses:

44 E BROADWAY BL

Inspection Status: Closed

Inspection History: FRAMING

Date Description Inspector Results Comments
08/12/2010 FRAMING Closed
07/25/2008 FRAMING Approved IVRS - Inspection :*
07/21/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
CANCELED BY LONNIE
06/20/2008 FRAMING Partial Approval IVRS - Inspection :*
A. RETAIL SHOP AREA 1ST FLOOR OK TO COVER ALSO
B. PLEASE HAVE RFI FOR CHANGE IN FRAMING PUT IN PLAN
C. CAUTION - YOU MUST MAINTAIN FLEXURE AT TOP OF WALL
D. LINE 2/A-D FRAMING OK TO COVER
06/19/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
NOT READY 11 AM SEE NOTES/SITE LOCKED ON RETURN VISIT @ 2:30 PM

1. NO ACCESS TO ANY APPROVED PLANS
2. NO SUPERINTENDENT ON SITE
3. NO SUB-CONTRACTOR FOR FRAMING ON SITE
06/12/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
PLEASE MAKE CORRECTIONS NOTED ON 1ST INSPECTION

YOU MUST PAY A REINSPECTION FEE @ 201 N. STONE
06/10/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE PREVIOUS CORRECTION NOTES A REINSPECTION FEE WILL BE ASSESSED IF PROGRESS IS NOT MADE
05/23/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1ST FLOOR RETAIL SHOP - FOLLOW PLANS FOR FIRE WALL

1. CAUTION CLOSET FLANGES ARE 19" FROM ROUGH BUT WILL NEED TO BE 16"-18" AT FINISH
2. YOU NEED TO FLEX AT TOP OF WALL SEE DETAIL 3 AO.02