Inspection History Details
Inspection Status: Closed
Inspection History: FRAMING
Permit Number - T05CM04911
Inspection Description - FRAMING
Inspection Status - Closed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2010 | FRAMING | Closed | ||
| 07/25/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/21/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* CANCELED BY LONNIE |
|
| 06/20/2008 | FRAMING | Partial Approval | IVRS - Inspection :* A. RETAIL SHOP AREA 1ST FLOOR OK TO COVER ALSO B. PLEASE HAVE RFI FOR CHANGE IN FRAMING PUT IN PLAN C. CAUTION - YOU MUST MAINTAIN FLEXURE AT TOP OF WALL D. LINE 2/A-D FRAMING OK TO COVER |
|
| 06/19/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* NOT READY 11 AM SEE NOTES/SITE LOCKED ON RETURN VISIT @ 2:30 PM 1. NO ACCESS TO ANY APPROVED PLANS 2. NO SUPERINTENDENT ON SITE 3. NO SUB-CONTRACTOR FOR FRAMING ON SITE |
|
| 06/12/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* PLEASE MAKE CORRECTIONS NOTED ON 1ST INSPECTION YOU MUST PAY A REINSPECTION FEE @ 201 N. STONE |
|
| 06/10/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE PREVIOUS CORRECTION NOTES A REINSPECTION FEE WILL BE ASSESSED IF PROGRESS IS NOT MADE |
|
| 05/23/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1ST FLOOR RETAIL SHOP - FOLLOW PLANS FOR FIRE WALL 1. CAUTION CLOSET FLANGES ARE 19" FROM ROUGH BUT WILL NEED TO BE 16"-18" AT FINISH 2. YOU NEED TO FLEX AT TOP OF WALL SEE DETAIL 3 AO.02 |