Permit: T05CM04907

Parcel: 118121450


Addresses:

1300 S 2ND AV #01

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/15/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*TUB TEST OK
NO CONCRETE HAS BEEN POURED TO FILL TUB BOX OUTS.
12/14/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3 OF 4 TUB WASTES OK
2) HALL BATH IN 3 BED ROOM UNIT
3) HAS A LEAKING OVERFLOW GASKET
4) LEAK EXPOSED AND RECALL FOR INSPECTION
12/12/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO TEST ON TUBS - FILL TUBS ABOVE OVERFLOW
COVER FOR TEST ON OVERFLOW GASKET
NOTE: OVERFLOW NOT CENTERED ON HOLE - GAP ON TOP
12/08/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WATER TEST ON WASTE & VENT (OK)
WATER-RUN TEST REQUIRED FOR WASTE & OVERFLOW
REMOVE TEST PLUGS FROM TUB - FILL TUBS TO OVERFLOW LEVEL FOR WASTE & OVERFLOW INSPECTION.
2. INSTALL GAUGE ON WATER PIPING FOR INSPECTION - REMOVE DEAD LEG FROM PIPING.
3. OVERHEAD HORIZONTAL ABS REQUIRES SUPPORT AT CHANGE OF DIRECTION.
(NOTES FOR 1300 S. 2ND AV) --
WATER PIPING TEST AT 70+PSI (OK)
WASTE & VENT WATER TEST - OK
CLOSET FLANGES INSTALLED - OK
OK TO COVER ALL EXCEPT BEHIND TUBS - CALL FOR WASTE & OVERFLOW INSPECTION, HAVE TUBS FULL TO OVERFLOW FOR INSPECTION
12/05/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*PROVIDE TEST ON WASTE.PROVIDE GAGE FOR TEST ON WATER.
12/01/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| DETAILED LIST OF CORRECTIONS
PROVIDE TEST ON WASTE & VENT
PROVIDE TEST ON WATER. USE GAUGE.
SUPPORT HORIZONTAL ABS AT CHANGE OF DIRECTIONS
SECURE SHOWER RISER-ADAPATOR
PROVIDE TEST ON RISER
SECURE ?? HB ADAPTORS
NOTE: BRASS OR COPPER WILL BE REQUIRED BETWEEN ADPT & HB.
PROVIDE 2 % SLOPE ON WASHER TRAP ARMS
PROVIDE CORRECT CLEAN OUT FITTING AT WASHER
A SANITARY T IS NOT APPROVED IN AN HORIZONTAL POSITION FOR DRAINAGE PIPING