Permit: T05CM04907

Parcel: 118121450


Addresses:

1300 S 2ND AV #01

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/28/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1) PLAN SPECS SCHEDULE 40 PVC FOR YARD WATER PIPING
2) PEX PIPING IS OK IF ACCEPTED BY ARCHITECT
3) PROVIDE A STAMPED LETTER, AND RED LINE PRINTS
4) HCS IS OK
5) NOTIFY SW GAS TO REPAIR COATING ON GAS PIPE
10/31/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
10/28/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
10/25/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*WATER TEST NORTH UNIT THRU 2 WAY CLEANOUT SEWER TURNS SOUTH RUNS APP'30 (3") OK
WATER TEST SOUTH UIT THRU 2 WAY CLEANOUT INTO BUILDING OK
WILL NEED TO VIEW PIPE WRAPS PRIOR TO CONCRETE
WILL NEED TO VIEW CONTINUATION OF NORTH 3" SEWER THRU TIE INTO SOUTH UNIT TO HCS CONNECTION WITH TEST.
10/24/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :* PROVIDE 1/4" PER FOOT FALL ON ALL PIPING.
PROVIDE WATER TEST OR AIR TEST TO 10'
PROVIDE SHADEING ON ALL PIPING
10/23/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*