Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T05CM04860

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/21/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES 2ND FLOOR POD #2 & WOOD AREA 2ND FLOOR.
09/18/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
EAST, SOUTH, WEST & WOOD AREA, OK TO COVER.

2ND FLR. FIRST POD, OK TO COVER GRID.
09/14/2006 MECHANICAL - ABOVE CEILING Partial Approval 1. 1ST FLOOR SOUTH END -- OK TO COVER GRID
2. FC-12 FIRE CONTROL ELECT. PINET. BOX
NEED TO RE-ROUTE FOR CLEAR ACCESS TO FAN COIL.
09/12/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED FOR FAN COIL ACCESS AT FCU-2
08/30/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1ST FLR.
PAD #2/3 EAST WEST CORRIDORS, OK TO COVER

1. FCU-2 ISOLATE CU FROM STEEL.
2. FCU 12 - CLEAR ACCESS FROM SPKR. & ELECT. CONDUIT,
J BOX

2ND FLR. NW CORNER, CORRIDOR, STAFF LOUNGE, PHARMACY. OK FOR CEILING TILES.
08/18/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. 2ND FLOOR SW CORNER HARD LID
OK TO COVER
07/28/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SOUTH ADDN. WEST SIDE CORRIDOR
OK TO COVER HARD LID PORTION
07/07/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
NORTH POD OK FOR CEILING TILES, AS PER ROLEF DAWSON
SOUTH POD AREA OVER HARD LID. OK TO COVER.
ELEV. EQUIP. RM. FC#12. UNABLE TO ACCESS, REMOVE BLOWER/ACCESS PANELS W/SPRINKLER. ISOLATE COPPER LINES FROM STEEL.
06/26/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 2ND FLOOR SOUTH-117 PSI
2) 2ND FLOOR SOUTH POOL MECH SUPPLY EXHAUST DUCTS, REST ROOMS HARD LIDS OK TO COVER