Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM04860
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/12/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CU-1/2 17.8 MAX. 30 SELECT SW. CU-3 -- ID SWITCH AT UNIT 40/50 CU-5 CU-6 -- I.D SWITCH AT COND. 20/30 PHARMACY HOODS W/STAINLESS EXH. PIPE, ETC. STILL INCOMPLETE. HEPA FILTERS -- SEISMIC WIRING?? |
|
09/13/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/28/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED RESTROOMS SUPPLY OVER HARD LID |
|
06/20/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLR 3RD POD 120 PSI FEED FROM 1ST FLR. UP THRU CHASE! |
|
06/07/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLR. NORTH END 118 PSI RISER UP TO 2ND FLR. POD #2 INTERMEDIATE - EAST AND WEST SIDE VAV301 REPLACE VALVE ASSY. 144 PSI |
|
05/19/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLR. SOUTH - PRESS TEST - 120 PSI |
|
05/18/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 2ND FLOOR HARD LID REST RMS., OK TO COVER 2. WALKED ROOFTOP RAIN HANDLERS ON PACKAGES |
|
05/16/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NORTH EXPANSION TO SOUTH GRID LINE 12 TO 3" ISOLATION VALVES; 1ST FLOOR |
|
05/10/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD POD 1ST FLR. 125 PSI OK NOTE! ALL REFRIG. LINE BUNDLES MUST BE TOTALLY ISOLATED FROM ALL STEEL STRUCTURES - HANGERS, ETC. |
|
05/02/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND POD - 1ST FLR. 120 PSI |
|
04/27/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED HOT WATER PIPING LEVEL I POD 3 TO VAV'S PIPING IN SHAFTS 2,3 & 4 ALL OK TO INSULATE & COVER. |
|
04/21/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 1ST FLR. HARD LID REST RM. CEILINGS, OK TO COVER. 2. FAN COIL - ELECT. RM. 1ST FLR. NEED ACCESS CLEARED. |
|
04/14/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HORIZONTAL SUSPENDED A/H MAINTAIN CLEAR ACCESS TO FRONT PANELS. |
|
03/03/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED V.A.V.'S 1ST FLOOR NORTH POD RELOCATE VAV #413 FOR ACCESS OK TO PROCEED |
|
02/17/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSPECTED 4" HOT WATER PIPING SUPPLY & RETURN 1ST FLOOR ONLY OK TO INSULATE |
|
02/15/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR SUSPENDED SUPPLY DUCTS PROGRESSING |
|
02/08/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*WALKED 1ST & 2ND FLOOR DUCT SYSTEMS PROGRESSING PORTIONS WRAPED |