Permit: T05CM04860

Parcel: 11202034A


Addresses:

3838 N CAMPBELL AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05CM04860

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/12/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CU-1/2 17.8 MAX. 30

SELECT SW. CU-3 -- ID SWITCH AT UNIT 40/50
CU-5
CU-6 -- I.D SWITCH AT COND. 20/30

PHARMACY HOODS W/STAINLESS EXH. PIPE, ETC. STILL INCOMPLETE.
HEPA FILTERS -- SEISMIC WIRING??
09/13/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/28/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED RESTROOMS SUPPLY OVER HARD LID
06/20/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLR 3RD POD 120 PSI
FEED FROM 1ST FLR. UP THRU CHASE!
06/07/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLR. NORTH END 118 PSI
RISER UP TO 2ND FLR.
POD #2 INTERMEDIATE - EAST AND WEST SIDE
VAV301 REPLACE VALVE ASSY.
144 PSI
05/19/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLR. SOUTH - PRESS TEST - 120 PSI
05/18/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 2ND FLOOR HARD LID REST RMS., OK TO COVER
2. WALKED ROOFTOP RAIN HANDLERS ON PACKAGES
05/16/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
NORTH EXPANSION TO SOUTH GRID LINE 12 TO 3" ISOLATION VALVES; 1ST FLOOR
05/10/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD POD 1ST FLR.
125 PSI OK
NOTE! ALL REFRIG. LINE BUNDLES MUST BE TOTALLY ISOLATED FROM ALL STEEL STRUCTURES - HANGERS, ETC.
05/02/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND POD - 1ST FLR.
120 PSI
04/27/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED HOT WATER PIPING LEVEL I POD 3 TO VAV'S PIPING IN SHAFTS 2,3 & 4 ALL OK TO INSULATE & COVER.
04/21/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 1ST FLR. HARD LID REST RM. CEILINGS, OK TO COVER.
2. FAN COIL - ELECT. RM. 1ST FLR. NEED ACCESS CLEARED.
04/14/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
HORIZONTAL SUSPENDED A/H MAINTAIN CLEAR ACCESS TO FRONT PANELS.
03/03/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED V.A.V.'S 1ST FLOOR NORTH POD
RELOCATE VAV #413 FOR ACCESS
OK TO PROCEED
02/17/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSPECTED 4" HOT WATER PIPING SUPPLY & RETURN 1ST FLOOR ONLY OK TO INSULATE
02/15/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 1ST FLOOR SUSPENDED SUPPLY DUCTS PROGRESSING
02/08/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*WALKED 1ST & 2ND FLOOR
DUCT SYSTEMS PROGRESSING PORTIONS WRAPED