Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
Permit Number - T05CM04860
Inspection Description - PLUMBING - MEDICAL GAS/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/14/2006 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* SPECIAL INSPECTOR HAS APPROVED ALL REQ'D TESTING |
|
05/03/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 2ND FLOOR OK OK TO COVER SUBJECT TO SPECIAL INSPECTOR RECALL 03045 AFTER ALL TESTING COMPLETE |
|
04/27/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1. 2ND FLOOR MED GAS LABELIING GOING OK - CALL ONE MORE TIME BEFORE SHEETROCK. |
|
03/17/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* FIRST FLOOR OK TO COVER SUBJECT TO TEST RESULTS FROM SPECIAL INSPECTOR. |
|
02/27/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
02/24/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
02/15/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 150 PSI NITROGEN TEST ON 1" 02 FROM CLEAN SUPPLY 1651 EMERGENCY O2 SUPPLY CABINET AND 1" TO UNDERGROUND NOTE #5 P2.01C, CONTINUES TO ZONE CONTROL VALVE AT WEST WALL OF EQUIP 1421 THRU TO PROC. #12233, #1422, #1320 PER PLAN WITHOUT ABOVE CEILING VALVE SHOWN ABOVE ZONE BOX. 1" CONTINOUS PER PLAN TO EXAM CONSULT 1415 TO 2ND LEVEL ABOVE CEILING IN LINE VALVE WHICH IS CLOSED AT THIS INSPECTION. IN WALL OUTLETS ARE NOT CONNECGTED AT THIS TIME | |
01/23/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 2ND FLOOR STILL REQUIRES CORRECTION LACKING LABELS PLEASE CALL AGAIN IN A COUPLE OF DAYS |
|
01/20/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 1. SECOND FLOOR OVERHEAD 1" TYPE "K" UNDERGROUND, INSIDE SLEEVE OK TO COVER SUBJECT TO 3RD PARTY INSPECTOR 1" WATER LINE TYPE "K" WITH SILFOS'D JOINTS OK |
|
01/10/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | FIRST FLOOR MAIN OVERHEAD OK , LABELS OK, HANGERS OK OVERHEAD ON FIRST FLOOR TO SECOND FLOOR OK. LABELS OK. HANGERS OK PLEASE CALL FOR INSPECTION WHEN INSTALLING UNDERGROUND, AND FOR SECOND FLOOR PIPING |
|
01/06/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 1) MEDICAL GAS PRE-CON MEETING SUN MECH CITY OF TUCSON CACTUS MEDICAL DPR |