Permit: T05CM04860

Parcel: 11202034A


Addresses:

3838 N CAMPBELL AV


Inspection Status: Approved

Inspection History: PLUMBING - MEDICAL GAS/TEST

Permit Number - T05CM04860

Inspection Description - PLUMBING - MEDICAL GAS/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2006 PLUMBING - MEDICAL GAS/TEST Approved IVRS - Inspection :*
SPECIAL INSPECTOR HAS APPROVED ALL REQ'D TESTING
05/03/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
2ND FLOOR OK
OK TO COVER SUBJECT TO SPECIAL INSPECTOR
RECALL 03045 AFTER ALL TESTING COMPLETE
04/27/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1. 2ND FLOOR MED GAS
LABELIING GOING OK - CALL ONE MORE TIME BEFORE SHEETROCK.
03/17/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
FIRST FLOOR OK TO COVER SUBJECT TO TEST RESULTS FROM SPECIAL INSPECTOR.
02/27/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
02/24/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
02/15/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval 150 PSI NITROGEN TEST ON 1" 02 FROM CLEAN SUPPLY 1651 EMERGENCY O2 SUPPLY CABINET AND 1" TO UNDERGROUND NOTE #5 P2.01C, CONTINUES TO ZONE CONTROL VALVE AT WEST WALL OF EQUIP 1421 THRU TO PROC. #12233, #1422, #1320 PER PLAN WITHOUT ABOVE CEILING VALVE SHOWN ABOVE ZONE BOX. 1" CONTINOUS PER PLAN TO EXAM CONSULT 1415 TO 2ND LEVEL ABOVE CEILING IN LINE VALVE WHICH IS CLOSED AT THIS INSPECTION. IN WALL OUTLETS ARE NOT CONNECGTED AT THIS TIME
01/23/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval 2ND FLOOR STILL REQUIRES CORRECTION LACKING LABELS
PLEASE CALL AGAIN IN A COUPLE OF DAYS
01/20/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval 1. SECOND FLOOR OVERHEAD
1" TYPE "K" UNDERGROUND, INSIDE SLEEVE OK TO COVER SUBJECT TO 3RD PARTY INSPECTOR
1" WATER LINE TYPE "K" WITH SILFOS'D JOINTS OK
01/10/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval FIRST FLOOR MAIN OVERHEAD OK , LABELS OK, HANGERS OK
OVERHEAD ON FIRST FLOOR TO SECOND FLOOR OK. LABELS OK. HANGERS OK
PLEASE CALL FOR INSPECTION WHEN INSTALLING UNDERGROUND, AND FOR SECOND FLOOR PIPING
01/06/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval 1) MEDICAL GAS PRE-CON MEETING
SUN MECH
CITY OF TUCSON
CACTUS MEDICAL
DPR