Permit: T05CM04860

Parcel: 11202034A


Addresses:

3838 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04860

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
ALSO APPROVED #T05CM02678
NOTE: PARKING AREA LIGHTING NOT INSPECTED OR INCLUDED IN SCOPE OF WORK FOR THIS STRUCTURE.
11/27/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. STILL HAVE OVERFILED GUTTERS -- NEC 366.6 (OVER 30 CONDUCTORS) -- CORRECT TO COMPLY WITH 310.15 B2A OR 310.15 (C)
2. NEED SIGN @ SERVICE -- NEC 700.8
3. VALET BOOTH WIRING INCOMPLETE.
4. CHECK FLEX CONNECTOR APPROVAL FOR OVER 250 V
5. RE-ENERGIZE/REMOVE TEMPORARY WIRING

OK TEMP C OF O
11/22/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ALL CORRECTIONS ON BOTH PERMITS
2) IT APPEARS WIRING IS NOT COMPLETE IN SOME AREAS
3) HAVE ELECTRICIAN ON SITE TO PROVIDE ACCESS AND OPEN EQUIPMENT AS NEEDED
4) CALL BOTH PERMITS IN WHEN READY FOR FINAL
11/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/11/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. TRANSFORMER IN ROOM #1419 (TIA/N) TO CLOSE TO WALL -- NEC 110.3
2. SEAL ALL UNUSED OPENINGS IN ALL GUTTERS IN ELECTRICAL ROOMS AND DERATE CONDUCTORS IN GUTTERS AS NEEDED -- NEC 110.12A, 376.22
3. MAKE SURE ALL ENCLOSURES, GUTTERS ARE GROUNDED WITH PROPERLY SIZED EQUIPMENT GROUND -- NEC 250.148

OK TEMP C OF O
CORRECTIONS, WIRING ARE ONGOING

OK TO OCCUPY BUILDING FOR THE PURPOSE OF SETTING UP EQUIPMENT, STOCKING, ETC...

NOTE: LOCKOUT & TAG OR DO NOT LAND ON BREAKER ANY OPEN WIRING THAT MAY BECOME ENERGIZED. CONTINUE TO COMPLETE WIRING AND CORRECTIONS AND CALL FOR FINAL WHEN ALL IS FINISHED AND ALL EQUIPMENT IS INSTALLED.
10/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
CORRECTIONS IN PROGRESS
CLOSE OFF ALL OPEN WIRING ON INTERIOR & EXTERIOR THROUGHOUT
PARKING AREA LIGHTING NEEDS PLAN REVIEW, PERMIT AND INSPECTION.
10/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SERVICE ROOM
1. BOND ALL METALLIC PIPING TO SERVICE
NEC 250.104
2. BOND ALL REMOTE G.E BARS TO BUILDING STEEL
3. INSTALL ALL PANEL DIRECTORY'S & NUMBERS

MECHANICAL ROOM
1. SEAL ROOF PENETRATIONS
2. IDENTIFY ALL EQUIPMENT DISCONNECTS
3. BROKEN S.T FOR P2
4. INSTALL ALL FIXTURE BULBS
5. HAVE OPEN WIRING

REAR COURTYARD -- WIRING OPEN/INCOMPLETE
1. USE APPROVED FITTING FOR FLEX WITH OVER 250V
2. EXIT SIGN TO REAR COURTYARD?
10/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOFTOP INSPECTION
1. GROUND AND IDENTIFY ALL EQUIPMENT AND DISCONNECT.
2. INSTALL PROPER OVERCURRENT PROTECTION ON EQUIPMENT PER DATA PLATES FOR CU'S & EX. FANS

2ND FLOOR INSPECTION
1. PERMANENT PANEL DIRECTORYS AND MCC/PANEL IDENTIFICATION.
2. COMPLETE RECEPTION AREAS
3. BOX EXTENDERS AS NEEDED
4. CALCULATION ON GROUNDING ELECTRODE CONDUCTOR.

*NOTE:
ROOMS 2211 & 2517 ARE SHELLS ONLY - NO INSPECTIONS
LETTER FROM ARCHITECT CONCERNING DELETION OF LIGHTING SYSTEM RECEIVE TODAY.

NEXT INSPECTION: REMAINDER OF FIRST FLOOR AND EXTERIOR/COURTYARDS
PARKING LOT LIGHTING STILL NEEDS TO BE RESOLVED
START MAKING PLANS TO REMOVE TEMP SITE/TRAILER WIRING.
10/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FIRST FLOOR EXCEPT AS NOTED (INTERIOR)

ROOM #
1643 -- BOND BUSHING 250.97 LABEL DISCONNECT
1181, 1611 -- USE APPROVED FITTING WITH LB -
NOT CHASE NIPPLE
1421, 1320 -- PROPERLY BOND WIRE MOLD RACEWAY
LOBBY, 1200, 1300, 1400 -- FINISH RECEPTION AREA
1428 -- VERIFY LISTING OF X-RAY EQUIPMENT
1509 -- FINISH VDV'S, VERIFY LISTING FOR TUBE SYSTEM
1400, 1200 -- CHECK ELECTRIC ROOM & DATA ROOM
1181, 1508 -- APPROVED EXTENDER RINGS AT COMBUSTIBLES
1200 -- NEW VDV CABELING LAYING ON GRID
1183 -- FINISH ROOM
1154 -- FINISH CABLE TRAY
1126 -- MISSING SWITCH
1100 -- APPROVED EXTENDER RINGS IN COUNTER SPLASH 314.20
CHECK IN -- NO POWER TO ROLL-UP WINDOWS
CHECK FLOOR BOXES THROUGHOUT -- CLEAN EXCESS DIRT OUT OF PANELS XL185, LIC/N, LID/N -- NEED PERMANENT CIRCUIT DIRECTORY CLEAN EXCESS DIRT OUT OF .

RECEIVED CK#267 FOR $162.00 AFTER HRS. INSP.