Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/02/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
09/29/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
09/28/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
09/27/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
09/26/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. REMOVE ALL CEILING TILES ON 2ND FLOOR S.E. POD FOR INSPECTION -- CEILING IN THIS AREA NOT APPROVED FOR COVER. 2. PROPERLY SUPPORT CAT 5 ROOM #2121 N. WALL CEILING 1182, 1183 -- NR 2ND FLOOR -- FAR S.W AREA NR |
|
09/25/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. ROOM 2141 HAS CAT. 5 NOT PROPERLY SUPPORTED ALONG WEST WALL CEILING OK TO COVER REST OF ROOM. OK ROOMS 2143, FOOD SERVICE AREAS *NOTE: FRONT GROUND LIGHTS (EXTERIOR) DO NOT HAVE COVER APPROVAL AND DO NOT APPEAR TO MEET MINIMUM COVER REQUIREMENTS -- NEC 300.5 |
|
09/22/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER IN FOLLOWING CEILINGS #2134, 2136A, 2117, 2118, 2145, 2135 NOTE: WIRE NUTS TO BE USED AS LISTED - THEY ARE BEING OVERFILLED, CORRECT AS NEEDED ALSO, J-BOXES ARE BEING OVERFILLED, CORRECT AS NEEDED. |
|
09/21/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER 2ND FLOOR NORTH EAST POD 1. SOUTHEAST POD HAS OPEN J-BOXES MISSING FIXTURES 2. LOWER LEVEL NEED STRUT @ GUTTER, BOX EXTENSIONS, DERATE CONDUCTORS PER NEC 310.15 IN RACEWAYS. 3. USE WIRE NUTS AS LISTED -- NEC 110.3 |
|
09/13/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR CEILING COVER -- ROOM #2221 AND ALL THE WAY NORTH, WEST EXTERIOR UP TO EAST CORRIDOR. OK OFFICE AREA @ 1RST FLOOR RECEPTION SOUTHEAST AREA OK TO COVER EXTERIOR RECEPTION AREA GROUND LIGHTING RACEWAYS AS NEEDED. |
|
09/08/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RAY 730-1416 OK DROP CEILING COVER RECEPTION/LOBBY AREA NOTE: IN OTHER AREA'S REMOVE TEMP WIRING, CHECK BOX FILL & STRAPPING/SUPPORTS |
|
08/30/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN LOWER N-S CORRIDORS CEILINGS ELEVATOR TO ENTRY |
|
08/16/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN HARD LID ELEVATOR LOBBY AREA #2101 & CORRIDOR ALSO, OK CEILING COVER ROOMS 1506 THRU 1518 |
|
08/10/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LID CANS 1502/1407, 1502/1409, 1500/1327, 1500/1309, 1237/1236, 1237/1207, 2207/2517B, 2207/2517A, 2208/2401, 2304/2203, 2202/2301 1. JUNCTION BOXES TO BE ACCESSIBLE |
|
08/03/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN CEILING MIDDLE AREA - FAR SOUTH POD. *NOTE: PROVIDE LETTER FROM ENGINEER OUTLINING INTENT FOR BRANCH CKT UPSIZING -- PARTIAL APPROVAL SUBJECT TO ENGINEER APPROVAL OF PLAN CHANGE. |
|
07/28/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LID COVER S.W SECTION CEILING NOTE: PLAN CALLS FOR UPSIZED BRANCH CKT IN SEVERAL AREAS. VERIFY WITH ARCH. OR ENGINEER WHETHER OR NOT UPSIZING IS INTENDED TO GO ALL THE WAY TO DEVICE OR NOT. PROVIDE STAMPED LETTER |
|
07/27/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* BRANCH CKT WIRING IS NOT BEING INCREASED AS PLAN REQUIRES, NEC ALSO REQUIRES UPSIZED EQUIPMENT GROUND IF INCREASING UNGROUNDED CONDUCTOR SIZE NEC 250.122 |
|
07/26/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CENTER POD CEILING COVER NOTE: MAKE SURE BRANCH CKT UPSIZING IS PER PLAN SPECIFICATION |
|
07/21/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NORTH POD |
|
07/20/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK N.E AREA NORTH OF ELEVATOR |
|
07/18/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUPPORT ALL BOXES IN CEILING WITH WIRES. 2. FINISH VDV CABELING -- INSTALLING & SUPPORTING. 3. IF USING MANUFACTURERS CLIPS THEY MUST BE EFFECTIVE 4. IF USING SUPPORT WIRES THEY MUST BE AS PER 300.11 OK ROOM 1645, 1642 |
|
07/06/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER IN SUSPENDED CEILING HARD LIDS IN SOUTH ENTRY, 3 EAST PODS ALSO STAIRWALLS, PANTRY WALLS. |
|
07/03/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* GATE IS LOCKED -- NO ACCESS |
|
05/04/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER IN HARD LID CEILINGS EAST OF EAST CORRIDOR. |