Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM04860

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/02/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/29/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/28/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/27/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/26/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. REMOVE ALL CEILING TILES ON 2ND FLOOR S.E. POD FOR INSPECTION -- CEILING IN THIS AREA NOT APPROVED FOR COVER.
2. PROPERLY SUPPORT CAT 5 ROOM #2121 N. WALL CEILING
1182, 1183 -- NR
2ND FLOOR -- FAR S.W AREA NR
09/25/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. ROOM 2141 HAS CAT. 5 NOT PROPERLY SUPPORTED ALONG WEST WALL CEILING
OK TO COVER REST OF ROOM.
OK ROOMS 2143, FOOD SERVICE AREAS
*NOTE: FRONT GROUND LIGHTS (EXTERIOR) DO NOT HAVE COVER APPROVAL AND DO NOT APPEAR TO MEET MINIMUM COVER REQUIREMENTS -- NEC 300.5
09/22/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER IN FOLLOWING CEILINGS
#2134, 2136A, 2117, 2118, 2145, 2135

NOTE: WIRE NUTS TO BE USED AS LISTED - THEY ARE BEING OVERFILLED, CORRECT AS NEEDED
ALSO, J-BOXES ARE BEING OVERFILLED, CORRECT AS NEEDED.
09/21/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER 2ND FLOOR NORTH EAST POD
1. SOUTHEAST POD HAS OPEN J-BOXES MISSING FIXTURES
2. LOWER LEVEL NEED STRUT @ GUTTER, BOX EXTENSIONS, DERATE CONDUCTORS PER NEC 310.15 IN RACEWAYS.
3. USE WIRE NUTS AS LISTED -- NEC 110.3
09/13/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 2ND FLOOR CEILING COVER -- ROOM #2221 AND ALL THE WAY NORTH, WEST EXTERIOR UP TO EAST CORRIDOR.
OK OFFICE AREA @ 1RST FLOOR RECEPTION SOUTHEAST AREA OK TO COVER EXTERIOR RECEPTION AREA GROUND LIGHTING RACEWAYS AS NEEDED.
09/08/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
RAY 730-1416

OK DROP CEILING COVER RECEPTION/LOBBY AREA

NOTE: IN OTHER AREA'S REMOVE TEMP WIRING, CHECK BOX FILL & STRAPPING/SUPPORTS
08/30/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN LOWER N-S CORRIDORS CEILINGS ELEVATOR TO ENTRY
08/16/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN HARD LID ELEVATOR LOBBY AREA #2101 & CORRIDOR
ALSO, OK CEILING COVER ROOMS 1506 THRU 1518
08/10/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LID CANS 1502/1407, 1502/1409, 1500/1327, 1500/1309, 1237/1236, 1237/1207, 2207/2517B, 2207/2517A,
2208/2401, 2304/2203, 2202/2301

1. JUNCTION BOXES TO BE ACCESSIBLE
08/03/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN CEILING MIDDLE AREA - FAR SOUTH POD.
*NOTE: PROVIDE LETTER FROM ENGINEER OUTLINING INTENT FOR BRANCH CKT UPSIZING -- PARTIAL APPROVAL SUBJECT TO ENGINEER APPROVAL OF PLAN CHANGE.
07/28/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LID COVER S.W SECTION CEILING
NOTE: PLAN CALLS FOR UPSIZED BRANCH CKT IN SEVERAL AREAS. VERIFY WITH ARCH. OR ENGINEER WHETHER OR NOT UPSIZING IS INTENDED TO GO ALL THE WAY TO DEVICE OR NOT. PROVIDE STAMPED LETTER
07/27/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
BRANCH CKT WIRING IS NOT BEING INCREASED AS PLAN REQUIRES, NEC ALSO REQUIRES UPSIZED EQUIPMENT GROUND IF INCREASING UNGROUNDED CONDUCTOR SIZE
NEC 250.122
07/26/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CENTER POD CEILING COVER
NOTE: MAKE SURE BRANCH CKT UPSIZING IS PER PLAN SPECIFICATION
07/21/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
NORTH POD
07/20/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK N.E AREA NORTH OF ELEVATOR
07/18/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT ALL BOXES IN CEILING WITH WIRES.
2. FINISH VDV CABELING -- INSTALLING & SUPPORTING.
3. IF USING MANUFACTURERS CLIPS THEY MUST BE EFFECTIVE
4. IF USING SUPPORT WIRES THEY MUST BE AS PER 300.11

OK ROOM 1645, 1642
07/06/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER IN SUSPENDED CEILING
HARD LIDS IN SOUTH ENTRY, 3 EAST PODS
ALSO STAIRWALLS, PANTRY WALLS.
07/03/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
GATE IS LOCKED -- NO ACCESS
05/04/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER IN HARD LID CEILINGS EAST OF EAST CORRIDOR.