Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM04860
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/05/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL SINGLE NON GFI RECEPTACLE FOR GENERATOR BATTERY CHARGER. 2. INSTALL SIGN AT SERVICE EQUIPMENT PER NEC 700.8 3. INSTALL SIGN ON DOOR COVERING GENERATOR DISCONNECT. 4. GENERATOR TO HAVE MIN. 2 HR. FUEL SUPPLY -- NEC 700.12 B2 |
|
10/03/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CONDUCTORS IN ALL GUTTERS NEED TO BE DERATED PER NEC 366.6 2. ALL TRANSFORMERS TO HAVE MINIMUM CLEARANCE TO COMBUSTIBLES AS MARKED ON TRANSFORMER -- NEC 110.3 |
|
10/02/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ROOMS 1183, 1182 - PROVIDE LISTING INFORMATION FOR MOTOR/ROOM DIVIDER ASSEMBLY, CLEAN UP CONTROL WIRING TO CONTROLLER ENCLOSURE AND CORD TO MOTOR, CONTROLLER COVER BLOCKED BY CEILING WIRE IDENTIFY DISCONNECT OK CEILING COVER BOUTIQUE ROOM @ ENTRY AREA. NOTE: CORRECTION CONCERNING PARKING LOT LIGHTING ON 9/28/06 WILL REQUIRE NEW PLAN REVISION AND SUBMIT FOR DSD APPROVAL THROUGH PLAN REVIEW - WORK HAS BEEN DONE OUTSIDE OF APPROVED PLANS AND WITHOUT INSPECTION. |
|
09/29/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WILL CALL BACK FOR FOLLOWING MONDAY FOR INSPECTION. |
|
09/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE SEALED LETTER FROM ENGINEER CONCERNING ANY ALTERATIONS FROM APPROVED PLANS INCLUDING DELETION OF LIGHTNING PROTECTION SYSTEM AND BRANCH CIRCUIT CONDUCTOR SIZES. 2. EXTERIOR PARKING AREA LIGHTING IS PART OF THE APPROVED PLAN, BUT IS BEING INSTALLED AND WIRED BY ELECTRIC UTILITY (TEP) WITHOUT PERMIT OR INSPECTION. 3. SPACE ABOVE INTERIOR PANELS TO BE DEDICATED PER NEC 110.26 F1 |
|
09/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINDER 2ND FLOOR DROP CEILING COVER NOTE: ROOM 2517 IS SHELL ONLY AT THIS TIME PROVIDE SEALED LETTER FROM ENGINEER CONCERNING LIGHTING PROTECTION SYSTEM DELETION. |
|
06/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FINISH WIRING AND RACEWAYS 2) SUPPORT WIRING ABOVE SUSPENDED CEILINGS SO IT COMPLYS WITH NEC 300.11 3) REMOVE TEMP WIRING FROM AREAS TO BE INSPECTED NEC 527.3 PARTIAL INSPECTION ONLY |
|
06/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS FOR 2ND LEVEL SOUTH AREA, LOWER LEVEL WEST BATHS AND FOOD SERVICE EAST WALL. *NOTE: CHECK TO SEE IF YOU HAVE COMPLIANCE PROVISIONS FOR NEC 517.14 |
|
06/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER IN WALLS - SOUTH ENTRY & BATH AREAS NO FOOD AREA @ THIS TIME. |
|
05/31/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER WALLS LINE 10/11 ROOMS 214 - EAST END LEVEL MAIN LEVEL LINES 10/11 S.E. AREA NORTH OF STAIRS MARTIN 730-1414 |
|
05/25/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NO MORE THAN 360 DEGREES IN A RUN -- ROOM 2357 OK WALLS EXCEPT NORTH WALL ROOM #2357 COLUMN D TO A AND 7 TO 9 |
|
05/15/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* A - C.5 THROUGH GRID LINES 4 TO 6 OK ROUGH WALLS |
|
05/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS. 2. NO MORE THAN 360 DEGREE IN A CONDUIT RUN. OK STAIR #2 |
|
04/17/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL CEILING COVER ROOMS #1624, 1621, 1435, 1418, 1417, 1336, 1319, 1318 OK ELECTRICAL WALL COVER GRID LINE 1-6 & "E" TO CORR. 2206 |
|
03/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS IN AREAS - NORTHEAST CORRIDOR TO SOUTH COURT YARD ALL REMAINING AREAS FIRST FLOOR SOUTH COURTYARD AND NORTH. |
|
03/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK SERVICE WATER AND BUILDING STEEL BONDS, OTHER PIPING SYSTEMS YET TO BE BONDED. 2. OK TO COVER ELECTRICAL IN WALLS - SOUTH CENTRAL COURTYARD TO NORTH CENTRAL COURTYARD. 3. OK TO COVER 4/0 GENERATOR GROUND. |
|
03/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS - NORTH CENTRAL COURTYARD AND NORTH |
|
02/24/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |