Permit: T05CM04860

Parcel: 11202034A


Addresses:

3838 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM04860

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/05/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL SINGLE NON GFI RECEPTACLE FOR GENERATOR BATTERY CHARGER.
2. INSTALL SIGN AT SERVICE EQUIPMENT PER NEC 700.8
3. INSTALL SIGN ON DOOR COVERING GENERATOR DISCONNECT.
4. GENERATOR TO HAVE MIN. 2 HR. FUEL SUPPLY --
NEC 700.12 B2
10/03/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONDUCTORS IN ALL GUTTERS NEED TO BE DERATED PER NEC 366.6
2. ALL TRANSFORMERS TO HAVE MINIMUM CLEARANCE TO COMBUSTIBLES AS MARKED ON TRANSFORMER -- NEC 110.3
10/02/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOMS 1183, 1182 - PROVIDE LISTING INFORMATION FOR MOTOR/ROOM DIVIDER ASSEMBLY, CLEAN UP CONTROL WIRING TO CONTROLLER ENCLOSURE AND CORD TO MOTOR, CONTROLLER COVER BLOCKED BY CEILING WIRE
IDENTIFY DISCONNECT
OK CEILING COVER BOUTIQUE ROOM @ ENTRY AREA.

NOTE: CORRECTION CONCERNING PARKING LOT LIGHTING ON 9/28/06 WILL REQUIRE NEW PLAN REVISION AND SUBMIT FOR DSD APPROVAL THROUGH PLAN REVIEW - WORK HAS BEEN DONE OUTSIDE OF APPROVED PLANS AND WITHOUT INSPECTION.
09/29/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WILL CALL BACK FOR FOLLOWING MONDAY FOR INSPECTION.
09/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROVIDE SEALED LETTER FROM ENGINEER CONCERNING ANY ALTERATIONS FROM APPROVED PLANS INCLUDING DELETION OF LIGHTNING PROTECTION SYSTEM AND BRANCH CIRCUIT CONDUCTOR SIZES.
2. EXTERIOR PARKING AREA LIGHTING IS PART OF THE APPROVED PLAN, BUT IS BEING INSTALLED AND WIRED BY ELECTRIC UTILITY (TEP) WITHOUT PERMIT OR INSPECTION.
3. SPACE ABOVE INTERIOR PANELS TO BE DEDICATED PER
NEC 110.26 F1
09/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK REMAINDER 2ND FLOOR DROP CEILING COVER
NOTE: ROOM 2517 IS SHELL ONLY AT THIS TIME
PROVIDE SEALED LETTER FROM ENGINEER CONCERNING LIGHTING PROTECTION SYSTEM DELETION.
06/27/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) FINISH WIRING AND RACEWAYS
2) SUPPORT WIRING ABOVE SUSPENDED CEILINGS SO IT COMPLYS WITH NEC 300.11
3) REMOVE TEMP WIRING FROM AREAS TO BE INSPECTED NEC 527.3 PARTIAL INSPECTION ONLY
06/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS FOR
2ND LEVEL SOUTH AREA,
LOWER LEVEL WEST BATHS AND
FOOD SERVICE EAST WALL.
*NOTE: CHECK TO SEE IF YOU HAVE COMPLIANCE PROVISIONS FOR NEC 517.14
06/09/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER IN WALLS - SOUTH ENTRY & BATH AREAS NO FOOD AREA @ THIS TIME.
05/31/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER WALLS LINE 10/11
ROOMS 214 - EAST END LEVEL
MAIN LEVEL LINES 10/11 S.E. AREA NORTH OF STAIRS
MARTIN 730-1414
05/25/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NO MORE THAN 360 DEGREES IN A RUN -- ROOM 2357
OK WALLS EXCEPT NORTH WALL ROOM #2357
COLUMN D TO A AND 7 TO 9
05/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
A - C.5 THROUGH GRID LINES 4 TO 6
OK ROUGH WALLS
05/12/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS.
2. NO MORE THAN 360 DEGREE IN A CONDUIT RUN.
OK STAIR #2
04/17/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL CEILING COVER ROOMS #1624, 1621, 1435, 1418, 1417, 1336, 1319, 1318
OK ELECTRICAL WALL COVER GRID LINE 1-6 & "E" TO CORR. 2206
03/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS IN AREAS - NORTHEAST CORRIDOR TO SOUTH COURT YARD ALL REMAINING AREAS FIRST FLOOR SOUTH COURTYARD AND NORTH.
03/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SERVICE WATER AND BUILDING STEEL BONDS, OTHER PIPING SYSTEMS YET TO BE BONDED.
2. OK TO COVER ELECTRICAL IN WALLS - SOUTH CENTRAL COURTYARD TO NORTH CENTRAL COURTYARD.
3. OK TO COVER 4/0 GENERATOR GROUND.
03/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS - NORTH CENTRAL COURTYARD AND NORTH
02/24/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*