Permit: T05CM04858

Parcel: 116201350


Addresses:

471 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04858

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
MR. JESUS TO TAKE CARE OF TWO COVERS FOR RE FED POLE BASE LIGHTS
12/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. UFER NOT INSPECTED AND MUST BE SECURED.
2. 4" CONDUITS REQUIRE GROUND BUSHINGS TO BE GROUNDED
3. LABEL MAIN DISCONNECTS AS TO PANEL THEY FEED.
4. #1 POLE BASES NEUTRAL & GROUND COMBINED
COVER MISSING - TAPE WHITE GREEN & TIE TO FRAME.
5. 2ND POLE BASE - CANNOT WRAP GROUND WIRE AROUND BOLT NEED LUG -- TAPE WHITE GREEN & ALSO RUN INTO FRAME GRD INSTALL COVERS