Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM04858
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* MR. JESUS TO TAKE CARE OF TWO COVERS FOR RE FED POLE BASE LIGHTS |
|
12/30/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/09/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UFER NOT INSPECTED AND MUST BE SECURED. 2. 4" CONDUITS REQUIRE GROUND BUSHINGS TO BE GROUNDED 3. LABEL MAIN DISCONNECTS AS TO PANEL THEY FEED. 4. #1 POLE BASES NEUTRAL & GROUND COMBINED COVER MISSING - TAPE WHITE GREEN & TIE TO FRAME. 5. 2ND POLE BASE - CANNOT WRAP GROUND WIRE AROUND BOLT NEED LUG -- TAPE WHITE GREEN & ALSO RUN INTO FRAME GRD INSTALL COVERS |