Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
Permit Number - T05CM04858
Inspection Description - ELECTRIC - OUTDOOR LIGHTING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/17/2006 | ELECTRIC - OUTDOOR LIGHTING | Approved | IVRS - Inspection :* | |
02/15/2006 | ELECTRIC - OUTDOOR LIGHTING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) OPEN ALL POLES FOR INSPECTION 2) PROVIDE MISSING POLE J-BOX COVERS 3) POLES NEED TO BE PROVIDED WITH AN EQUIPMENT GROUND AND GROUNDED PROPERLY (THE BARE CONDUCTOR THAT EXTENDS) TO THE POLE FOOTING IS NOT AN ACCEPTABLE EQUIPMENT GROUND NEC 250.4 (B) (4) |
|
12/28/2005 | ELECTRIC - OUTDOOR LIGHTING | Not ready for Inspection | IVRS - Inspection :* |