Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T05CM04858
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2006 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
12/30/2005 | ELECTRIC - UFER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*SERVICE LATERAL RACEWAYS TO BE BONDED PER NEC 250.66 ALL LINE SIDE OF SERVICE RACEWAYS, NEED TO HAVE GROUNDING SIZED PER NEC 250.66 PANEL A DISCONNECT NEEDS TO BE READILY ACCESSIBLE- NEXT PAGE SIZE DISCONNECT GROUND TAPS PER NEC 250.66 ( GROUNDING ELECTRODE) BOND SPRINKLER PIPE TO SERVICE INSTALL 2 GROUND RODS MAKE SITE LIGHTING CORRECTIONS |
|
12/28/2005 | ELECTRIC - UFER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROVIDE APPROVED SET OF PLANS FOR INSPECTION 2) PROVIDE ACCESS TO ALL EQUIPMENT FOR INSPECTION. HAVE ELECTRICIAN ON SITE TO OPEN EQUIPMENT AND BLDG |
|
12/02/2005 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999*DID NOT INSPECT UFER ( COVERED) NO UNDERGROUND TO INSPECT NO APPROVED PLANS. |