Permit: T05CM04858

Parcel: 116201350


Addresses:

471 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T05CM04858

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2006 ELECTRIC - UFER Approved IVRS - Inspection :*
12/30/2005 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*SERVICE LATERAL RACEWAYS TO BE BONDED PER NEC 250.66
ALL LINE SIDE OF SERVICE RACEWAYS, NEED TO HAVE GROUNDING SIZED PER NEC 250.66
PANEL A DISCONNECT NEEDS TO BE READILY ACCESSIBLE- NEXT PAGE
SIZE DISCONNECT GROUND TAPS PER NEC 250.66 ( GROUNDING ELECTRODE)
BOND SPRINKLER PIPE TO SERVICE
INSTALL 2 GROUND RODS
MAKE SITE LIGHTING CORRECTIONS
12/28/2005 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROVIDE APPROVED SET OF PLANS FOR INSPECTION
2) PROVIDE ACCESS TO ALL EQUIPMENT FOR INSPECTION. HAVE ELECTRICIAN ON SITE TO OPEN EQUIPMENT AND BLDG
12/02/2005 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*DID NOT INSPECT UFER ( COVERED)
NO UNDERGROUND TO INSPECT
NO APPROVED PLANS.