Permit: T05CM04797

Parcel: 141092670


Addresses:

6675 E LADONNA LN


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM04797

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2006 FRAMING Approved IVRS - Inspection :*
02/16/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) MAKE UP AIR DUCT NOT OUTSIDE
2) BLOCK DUCT BOOTS 3 SIDES
3) NAIL PROTECT RANGE HOOD DUCT
4) NON BEARING STUDS NOTCHED MORE THAN 40 PERCENT
5) NAIL PROTECT WIRES
6) DWV WATER TEST ONLY 4 FEET ABOVE FLOOR TEST TO ROOF
7) FIRE STOP REQUIRES 2 LAYERS OF 1/2" OSB
8) EXTERIOR CLIP NOT APPROVED-YOU MUST CALL IT IN
9) STOPPED INSPECTION-TOO MANY ITEMS