Permit: T05CM04790

Parcel: 108240890


Addresses:

2474 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T05CM04790

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
12/19/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. BOXES NOT PROPERLY MOUNTED - NEC 314.23 B1 (SCREWS NOT ALLOWED ON BOX INTERIOR)
2. MC NOT PROPERLY SECURED/SUPPORTED - NEC 330.30 AND PROVIDE NAIL PLATES AS NEEDED - NEC 330.30
3. COMPLETE ALL WIRING PER PLAN (RECEP. AREA?)
4. MAX 360 DEG. ON RACEWAYS OR USE PULL BOX - NEC 300

OK TO BACKFILL SERVICE TRENCH.
12/15/2006 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
12/14/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE ALL OF SERVICE RACEWAY FOR INSPECTION
CAN'T BURY WITHOUT APPROVAL.
2. THEIR IS TO BE A WARNING RIBBON INSTALLED ALONG TRENCH -- NEC 300.5
07/25/2006 ELECTRIC - UNDERGROUND Partial Approval OK TO COVER FLOOR BOXES/SLAB
07/21/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UNDER SLAB -- EXTEND UFER TO SERVICE LOCATION