Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T05CM04790
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 12/19/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. BOXES NOT PROPERLY MOUNTED - NEC 314.23 B1 (SCREWS NOT ALLOWED ON BOX INTERIOR) 2. MC NOT PROPERLY SECURED/SUPPORTED - NEC 330.30 AND PROVIDE NAIL PLATES AS NEEDED - NEC 330.30 3. COMPLETE ALL WIRING PER PLAN (RECEP. AREA?) 4. MAX 360 DEG. ON RACEWAYS OR USE PULL BOX - NEC 300 OK TO BACKFILL SERVICE TRENCH. |
|
| 12/15/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
| 12/14/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSE ALL OF SERVICE RACEWAY FOR INSPECTION CAN'T BURY WITHOUT APPROVAL. 2. THEIR IS TO BE A WARNING RIBBON INSTALLED ALONG TRENCH -- NEC 300.5 |
|
| 07/25/2006 | ELECTRIC - UNDERGROUND | Partial Approval | OK TO COVER FLOOR BOXES/SLAB | |
| 07/21/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK UNDER SLAB -- EXTEND UFER TO SERVICE LOCATION |