Permit: T05CM04786

Parcel: 140260630

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05CM04786

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
01/13/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*ACCESS OPENING TO ACCESS FURNACE MUST BE MIN. 20"X 30"
REPLACE DAMAGED DRYER VENT
FURNACE VENT STILL NOT ADEQUATE CLEARANCE FROM ROOF SHEATHING
01/09/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FURNACE AND WATER HTR B-1 VENTS ARE TO CLOSE TO ROOF SHEET/COMBUSTIBLES
2) THESE ARE PROBABLY BEING MOVED BY THE ROOFERS. THESE PEOPLE NEED TO START BEING RESPONSIBLE FOR MATERIAL AT ROOF PENETRATIONS, PROPER POSITIONING OF VENTS, ETC...