Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM04786
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2006 | FRAMING | Approved | IVRS - Inspection :* | |
01/13/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1. FIRE STOP ABOVE CEILING 2. METAL BOX FOR FRIDGE |
|
01/09/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE LISTED ASSEMBLY FOR PLASTIC REFRIDGERATOR WATER SUPPLY BOX 2) YOU MAY NOT USE PLASTER RINGS FOR DATA CABLES IN A RATED WALL 3) I NEED TO SEE FIRESTOP FOR PENETRATIONS ABOVE CEILING IN FIREWALL 4) PROVIDE COPY OF FIRESTOP SYSTEMS YOU WISH TO USE FOR YOUR PENETRATIONS |