Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM04767
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/07/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ALL PIPING OK TO COVER, EXCEPT THAT FINAL APPROVAL IS PENDING PLAN REVISION FOR THE USE OF AIR ADMITTANCE VALUE AT KITCHEN SINK LOCATION. LETTER RECEIVED FROM DR. HORTON DESIGNER D. CUCCI AUTHORIZING USE OF AAV |
|
02/06/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO TEST ON DWV PROVIDE TEST ON DWV USE OF AIR ADMITTANCE VALVE FOR KIT SINK WILL REQUIRE A PLAN REVISION. PLEASE RED LINE PLAN TO REFLECT PIPING SYSTEM INSTALLATION |
|
02/03/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLAN SHOWS KIT SINK VTR INSTALL PER PLAN OR REVISE. HORIZONTAL VENTING BELOW FLOOD RIM IS ALLOWED IF DRAINAGE FITTINGS ARE USED. DRAINATE FITTINGS REQUIRED ON HORIZONTAL TO HORIZONTAL CHANGE OF DIRECTION PROVIDE TEST ON TUB OVERFLOW |