Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/30/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT 52 OK |
|
| 08/29/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* - PROVIDE LISTING FOR ABS FP OR USE PLASTIC MALE THREADS INTO FP METALLIC THREADS OR USE LISTED ADAPTOR COUPLING. - CORRECT DRIP ON INTERIOR SOV. SECURE CLOSET WATER SUPPLY |
|
| 07/27/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT 57 OK |
|
| 07/19/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 46 - OK ALL HBS BUILDING NEED VAC BREAKERS TO PROTECT OCCUPIED UNITS |
|
| 07/17/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LAUNDRY AT 50 AND 51 OK #46 - CORRECT SLOPE ON KS DO NOT STRAIN C O PIPING |
|
| 07/11/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 50 & 51 LAUNDRY; C O EXT REQUIRES WYE PATTERN FITTING DUAL OUTLET WB REQUIRED IF CONDENSATE DRAINS TO IT PROVIDE HOSE TO RUN TEST SECURE HB |
|
| 06/15/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) #47, #48 AND #60 OK TO COVER 2) SECURE DIVERTER VALVES IN A MANNER THAT WILL KEEP VALVES SQUARE WITH WALL AND TUB |
|
| 06/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNITS #45 & #49 OK TO COVER WALLS KITCHEN EXTENSION MADE OK |
|
| 05/04/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 50 & 51 OK TO COVER INSIDE WASHERS NOT READY |
|
| 05/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 55 & 56 OK TO COVER |
|
| 04/26/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 56 INSIDE OK TO COVER, PROVIDE RUN TEST ON WASHER 55 WASHER OK, INSIDE USE MISSION COUPLINGS SWEEP ON LAV AND SNAKE AND RETEST TUB |
|
| 04/24/2007 | PLUMBING - INTERMEDIATE | Cancelled | ||
| 04/19/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEW WORK AT WASHER BOX NOT ACCEPTABLE WHEN NEW WORK IS DONE IT MUST BE BROUGHT UP TO CODE 2 X 1 1/2 RESTRICTION & FURNCO COUPLINGS NOT ALLOWED CLEANOUT REQUIRED SECURE WATER PIPING AND WASTE SAFETY PLATE PIPING WITHIN 1 1/4" MISSION COUPLINGS REQUIRED AT TRANSITIONS. SECURE COPPER AT SINK AND LAV TEST SHOWER RISERS CAP OPEN PIPES SWEEPS REQUIRED ON HORIZONTAL CHANGES OF DIRECTION |
|
| 03/30/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT #59 OK TO COVER SOLVENT WELD WASTE INSTALLED RUN TEST TUB DRAIN |
|
| 09/21/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNIT #44. SECURE SHOWER VALVE IN WALL, OK TO COVER AFTER SECURING. BE SURE TO LEAVE ACCESS TO SLIP NUT TUB WASTE & OVERFLOW. |
|
| 09/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - UNIT 44 COMPLETE INSTALLATION OF HB VAC BREAKERS -- BREAK LOCK SCREW. - USE PROPER TRANSITION COUPLING AT C1 TO PL TRANSITION (MISSION COUPLING) - GALV NIPPS NOT ALLOWED AT LAUNDRY STUB OUT, ALSO SECURE DROP EAR ELLS. |
|
| 09/13/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SPOKE W/CONTRACTOR ON SITE; STEVE AND TOM LOPEZ. I HAVE ASKED YOU TO POST UNIT NUMBERS, MOST UNITS ARE NOT IDENTIFIED. UNIT #54 IS OCCUPIED, I HAVE NOT DONE A FINAL INSPECTION IN THIS UNIT. UNIT #58 IS A FURNISHED MODEL. I HAVE NOT INSPECTED THIS UNIT. ON MY INITIAL INSPECTION TO THIS PROPERTY I INFORMED YOU THAT YOUR WATER SYSTEM IS NOT PROPERLY PROTECTED AGAINST BACKFLOW. YOU HAVE MANY HOSE BIBS WITHOUT VACUUM BREAKERS. THE WATER SUPPLY TO YOUR IRRIGATION SYSTEM IS NOT PROPERLY PROTECTED. I EXPECT YOU TO CORRECT THIS IMMEDIATELY. CONTINUED NOT READYS WILL RESULT IN REINSPECTION FEES. |
|
| 08/25/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* UNIT #29 IS NOT ON THIS ACTIVITY |
|
| 08/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - UNIT #54 ONLY INSPECTED -- OK TO COVER - SUPPORT PIPING W/CABINET FRAME - NEW TUB DIVERTER OK - PLEASE PERMANENTLY IDENTIFY EACH UNIT FOR INSPECTION PURPOSES. |
|
| 08/11/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* POST ADDRESS AND UNIT NUMBERS, THIS INSPECTION IS FOR #54 ONLY. 90 CHANGE OF DIRECTION ONLY ON TRAP ARM PLUMBERS TAPE IS NOT ACCEPTED ASA PIPE CLAMP |
|
| 07/27/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SEE NOTES FROM ACTIVITY ...4757 |