Permit: T05CM04760

Parcel: 11006159B


Addresses:

2861 N COLUMBUS BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/10/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING EXHAUST FANS
11/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
10/22/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 47 & 51
09/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #46, 48, STOI
09/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
#46 -
1. SECURE BACK WALL LIGHT
2. FINISH LAUNDRY ROOM
3. SECURE AND ATTACH GROUNDING CONDUCTOR OUTSIDE
4. INSTALL ALL STRANDS UNDER LUG AT PANEL

#57 - OK

#48 -
1. EXCESS PAINT ON DEVICE TERMINALS
2. INSTALL ALL STRANDS UNDER TERMINAL AT PANEL
3. BRING SIDE OF PANEL TO WITHIN 1/4" OF SURFACE
09/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ELECTRIC -- HAVE ELECTRICIAN CHECK UNIT FIRST
08/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK UNITS #45 AND 60 STOI
08/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
MISSING DEAD FRONTS 40, 42, 33
ATTACH 34 TO BUILDING

OK UNIT #37

OK ROOFS
08/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #49
OK #55

RECEIVED CK#1214 FOR $108.00
08/02/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
#55
1. BOXES MORE THAN 1/4" -- 314.20
2. IDENTIFY UNGROUNDED CONDUCTOR 200.7
07/31/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #58, 54, 44
07/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
#58
1. REVERSE GROUNDS & NEUTRALS

OK #53 SUBJECT TO OTHERS
07/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RECEIVED CHK# 1201
FOR $432.00

ALL ROOF UNITS - CHECK UNGROUNDED CONDUCTOR
IDENTIFICATION, SUPPORT OF SEAL TIGHT
LOOSE FITTINGS & LABELING OF UNITS

#44 -
A. OUTSIDE RECEPTACLE NOT GFCI PROTECTED
B. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
C. LABEL PANEL AS PER 404.8

#68
A. NEED A CONNECTOR AT HOOD FOR NM CABLE
B. SHEATHING TO BE 1/4" INTO HOOD COMPARTMENT
C. GROUND CONDUCTOR TO BE 3/4 OF TURN UNDER SCREW
D. LABEL PANEL AS PER 408.4

#54
A. BOXES MORE THAN 1/4" FROM BOX TO SURFACE
B. NM CABLE TO BE 1/4" INTO HOOD COMPARTMENT
C. CLEAN BUSS OF FOREIGN MATERIAL
D. LABEL PANEL AS PER 408.4
E. BREAKER TO BE LISTED FOR USE BY MANUFACTURE
F. SEPARATE GROUNDS & NEUTRALS

#53
A. CLEAN BUSS OF FOREIGN MATERIAL
B. IDENTIFY NEUTRAL CONDUCTOR
C. COMPLETELY IDENTIFY UNGROUNDED CONDUCTOR ENTIRE EXPOSED LENGTH
D. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
E. INSTALL HOOD CONNECTOR FOR NM CABLE
07/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
#44, 24 & 58 ARE OCCUPIED WITHOUT INSPECTIONS
07/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE
2. FINISH ITEMS 3 & 5
07/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL DRY WALL IN LAUNDRY ROOM
2. INSTALL OR BLANK OFF HOOD
07/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
#55
1. MISSING COVER PLATES
2. GFCI FOR OUTDOOR RECEPTACLE
3. USE PROPER GROUNDING AT HOOD - NOT UNDER MOUNTING COVER SCREW
4. WE HAVE ONE TOO MANY GFI'S IN KITCHEN CIRCUITS
5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RING
6. PANEL LABELING TO BE AS PER 408.4 -- NO ABBREVIATIONS
7. CONDUCTORS TO BE UNDER TERMINAL SCREWS
06/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
06/01/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #56
05/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CLEAN EXCESS PAINT FROM TERMINALS
2. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL
3. TIGHTEN LOOSE CONNECTORS
4. INSTALL ALL STRANDS UNDER TERMINAL LUG
5. REMOVE OLD UNUSED DISCONNECT UNDER SERVICE AND PLUG HOLE.
05/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY WARD
05/22/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINAL #59
05/18/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS.
2. CLEAN EXCESS PAINT FROM BUSS & TERMINALS IN SUB-PANEL
3. INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINALS

ROOF:
1. MAINTAIN WORKING CLEARANCES
2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
3. TIGHTEN LOOSE FITTINGS

#45:
1. MISSING HOOD
2. BOXES 314.20
3. CLEAN PANEL
4. TERMINATE ALL GROUNDS

#60
1. MISSING FRONT PORCH LIGHTS
2. TIGHTEN LOOSE RECEPTACLES
3. BOXES 314.20
08/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ELECTRICAL CONTRACTOR TO BE ON SITE AT ANY ELECTRICAL INSPECTION.
2. RECEPTACLES NOT PROPERLY GROUNDED
3. OK RECEPTACLE AT KITCHEN PENINSULA IS NOT GFCI PROTECTED
4. HOOD NEEDS PROPER CONNECTION
5. OK SEAL UNUSED OPENINGS IN PANEL
6. PROPERLY I.D PANEL
7. FINISH JOB
8. SHEET METAL SCREWS NOT ACCEPTABLE IN PANEL
9. PANEL HAS OVERSPRAY AT BUSSING
10. INSTALL STRAIN RELIEF AT DRYER CORD
11. GFCI REQUIRED FOR OUTDOOR RECEPT.
08/03/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK EXISTING GUTTER & TAPS REPLACES EXISTING RISER CONDUCTORS PER PLAN