Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*. 1) OK #50 SUBJECT TO BLDG INSPECTOR 2) VERIFY DRILLING OF TRUSSES |
|
| 08/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SPLIT BOLT LISTED FOR A RUN & A TAP CONDUCTOR OK ROUGH #52 |
|
| 07/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 46 & 47 ROUGH |
|
| 07/24/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* #47 & 47 1. PROTECT FEEDERS AT TOP PLATE 2. STAPLE NM CABLE 8" TO SINGLE GANG 12" OTHERS |
|
| 07/19/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH 48 & 57 |
|
| 06/29/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK LAUNDRY ROOM #50 & #51 UNITS 53, 52, 51 & 50 OK TO CLOSE UP SERVICES 1. NEED CITY STAMP FOR PLANS OF SERVICE 2. CLEARANCES SUBJECT TO L.HANLY |
|
| 06/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH #60 |
|
| 06/22/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE PROVIDE A DRAWING TO VERIFY SERVICE LOADS AND CONDUCTOR SIZES. 2. INSTALL SERVICE ENTRANCE CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS 3. NOTE WATER BOND POINT TO BE ACCESSIBLE 4. FINISH PREVIOUS ITEMS #2,3,8 |
|
| 06/18/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PLEASE RESCHEDULE SO ELECTRICIAN CAN ACCESS SERVICE #60 1. LAUNDRY ROOM: CEILING BOX IS OVERFILLED 2. SECURE CABLES TO BOXES 312.5 ALSO, BRING FLUSH - ALSO, PLASTIC BOXES 3. PROPERLY GROUND BOXES 4. SECURE CABLES ABOVE PANEL 5. TIGHTEN LOOSE FITTINGS 6. CORRECTLY IDENTIFY GROUNDED CONDUCTORS 7. USE PROPER TOOLS TO CRIP COPPER SPLICES 8. USE APPROVED SCREWS TO MOUNT BOXES |
|
| 05/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. HAVE BUILDING INSPECTOR CHECK FOR FIREWALL SEPARATION. 2. FINISH LAUNDRY ROOM OK ROUGH 51 EXCEPT AS NOTED. |
|
| 04/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS UNIT 55 & 56 2. COMPLETE ITEM #6 FROM INSPECTION ON 4/19/07 FOR UNITS 55 & 56 |
|
| 04/24/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* STOP DRYWALL FINISH PREVIOUS INSPECTION ITEMS |
|
| 04/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT NM CABLES AS PER CODE 2. WE HAVE BOXES OVERFILLED 3. GROUND METAL BOXES 4. SECURE CABLES TO BOXES IN MULTI-GANG BOXES 5. SUPPORT CABLES ABOVE PANEL 6. SEPARATE GROUNDS & NEUTRAL AT SUB-PANEL 7. WHERE ARE PLANS FOR NEW LAYOUT 8. TIGHTEN LOOSE FITTINGS 9. WIRE SHEATH TO EXTEND 1/4" INTO BOXES |
|
| 03/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* #59 1. TIGHTEN NM CONNECTORS AT PANEL 2. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL OK WALLS OK LAUNDRY ROOM #58 |
|
| 07/28/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 601 ROUGH |