Permit: T05CM04758

Parcel: 11006159B


Addresses:

2821 N COLUMBUS BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/10/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING FIXTURE
2. MISSING EXHAUST FANS
3. MISSING SMOKE DETECTORS
11/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
KITCHEN COUNTERTOP RECEPTACLES TO BE GFCI PROTECTED
OK FINAL #26 STOI AND COMPLETION OF GFCI
10/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
10/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #B
08/22/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #21

1. FILL UNUSED OPENING IN BOTTOM OF PANEL
08/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO KEY TO ENTER
08/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #23
OK #10

RECEIVED CK#1214 FOR $108.00
08/02/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO WORK DONE
07/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RECEIVED CK#1201
FOR $432.00

#10
A. IDENTIFY NEUTRAL CONDUCTOR
B. CLEAN EXCESS DIRT FROM PANEL
C. LABEL PANEL AS PER 408.4

ALL ROOF UNITS - CHECK IDENTIFICATION OF UNGROUNDED CONDUCTOR, SUPPORT OF SEAL TITE, LOOSE FITTINGS AND LABELING OF UNITS.
07/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNIT 20 INSPECTED BY R.SUBA ON 8/4/06
OK UNIT 14 FINAL

1. CORRECTLY ID NEUTRAL A SUB-PANEL
2. CORRECTLY ID UNGROUNDED CONDUCTOR A/C DISCONNECT
07/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 215/24 + 216/25 INSPECTED ON 6/16/06
BY R.HOLLANDER
OK 213/22 ON 6/23/07
07/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO POWER RELEASE -
SUBJECT TO DETERMINATION OF L.HANLY
08/03/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ELEC. SERVICE REPLACED EXISTING RISER CONDUCTORS EXISTING GUTTER & TAPS OK
07/28/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK UNIT #203
2. LOOSE FITTINGS
3. SUPPORT SEALTITE
4. SPLIT BOLT LISTED 2 CONDUCTORS - A RUN & A TAP
5. A BOND BUSHING IS NEEDED 250.92