Permit: T05CM04757

Parcel: 11006159B


Addresses:

2801 N COLUMBUS BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 8 & 9 S.T.O.I

1. FINISH WORK TO OFFICE -- NEED ALL INSPECTION
12/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING SMOKE DETECTORS
2. MISSING EXHAUST FANS
11/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO COVER WALLS BEHIND SERVICES
ELECTRIC & FIRE BLOCKING
08/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEIVED CHECK #1250 FOR $108.00
08/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #3
08/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO ONE HOME #3
08/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #1
07/31/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH LABELING UNIT #1
07/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO WORK DONE
07/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
VERIFYING PAPERWORK
07/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RECEIVED CK#1201 -- $432.00

#3 -
A. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
B. BOND PANEL
C. LABEL PANEL AS PER 408.4
D. IDENTIFY NEUTRAL CONDUCTOR
E. PROTECT CONDUCTOR WITH A BUSHING
F. OUTSIDE RECEPTACLE NOT GFCI PROTECTED
G. GROUND SWITCHES
H. CHECK MAKE UP IN JUNCTION BOXES
I. ROOF: ID UNGROUNDED CONDUCTOR, STRAP SEALTITE, LOOSE FITTINGS

#7:
A. MISSING COUNTER RECEPTACLE
B. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
C. GROUND SWITCHES
D. OUTSIDE RECEPTACLE NOT GFCI PROTECTED
E. LABEL PANEL AS PER 408.4
F. BOND PANEL
G. MISSING DEAD FRONT COVER
H. PLEASE VERIFY SUB-PANEL AMPACITY

ALL ROOF UNITS
CHECK IDENTIFICATION OF UNGROUNDED CONDUCTORS, SUPPORT OF SEAL TITE, LOOSE FITTINGS & LABELING OF EMT'S
07/19/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNITS 4 & 5 INSPECTED 6/30/06
UNIT #1:
1. INSTALL CONNECTOR AT HOOD AND WIRING COMPARTMENT COVER
2. ANTI-TIP FOR RANGE
3. CORRECTLY LABEL PANELS 408.4 -- NO ABBREVIATIONS.
08/03/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ELEC. FINAL #6 #2