Permit: T05CM04747

Parcel: 12801005H

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM04747

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/03/2006 BUILDING - FINAL Approved PER PH CALL
01/26/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REFERENCE IBC SECTION 402.7.2 AND 708.4(4)
1. YOU ARE OPERATING WITHOUT A VALID C OF O. OWNER IS SUBJECT TO FINES OF $2500 PER DAY. OWNER SHOULD POST BOND FOR TCO TODAY!!
2. I NEED A COPY OF THE U.L. LISTED ASSEMBLY FOR CEILING
3. HAVE YOUR DESIGN PROFESSIONAL PROVIDE DETAIL FOR WHY TENANT SPACE IS OPEN TO NEIGHBORING TENANT ON WEST WALL ABOVE SOFFIT LINE & REVISE FOR CEILING IN EXIT CORRIDOR.
01/25/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
YOU ARE IN VIOLATION OF THE INTERNATIONAL BUILDING CODE. SPECIFICALLY YOU ARE OPERATION WITHOUT A VALID CERTIFICATE OF OCCUPANCY.
PLEASE OBTAIN A TEMPORARY C OF O BY POSTING A BOND WITH THE CITY OF TUCSON DEVELOPMENT SERVICES DEPARTMENTS AT 201 N. STONE BY END OF BUSINESS ON 1/26/06.
FURTHERMORE, PLEASE PROVIDE ALL PREVIOUSLY REQUESTED INFORMATION FOR A LISTED FIRE RATED CEILING AND A REVISED FIRE CORRIDOR PLAN WITHIN 3 BUSINESS DAYS OR ANY TEMPORARY C OF O MAY BE REVOKED.
12/23/2005 BUILDING - FINAL Partial Approval IVRS - Inspection :*OK TCO FOR STOCKING
I NEED AN U.L LISTED ASSEMBLY FOR 1 HOUR CEILING ( OR OTHER LISTING AGENCY) ALL YOU HAVE IS THAT TILE IS OK IN AN U.L ASSEMBLY
12/22/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*FINISH ALL WORK
VERTICAL GRAB BAR REQUIRES MORE SOLID SUPPORT IN RESTROOM
I NEED LISTED SYSTEM FOR T BAR 1 HR CEILING
PROVIDE FIRE AND ELECTRIC FINALS
12/13/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*YOU WILL NOT GET A C OF O WITHOUT A RATED CORRIDOR.