Permit: T05CM04747

Parcel: 12801005H

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Permit Number - T05CM04747

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2005 SHEET ROCK NAILING Approved IVRS - Inspection :*
12/07/2005 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) I NEED CORRECTIONS NOTED 11/30/05 FOR FRAMING. PLUS THOSE NOTED BELOW
2) THE SHEET ROCK ABOVE 12' ON WEST WALL OF RATED CORRIDOR IS UNACCEPTABLE. FIRE BARRIERS REQUIRE TIGHT CONSTRUCTION ALL THE WAY TO DECK
3) PROVIDE A LISTED FIRE STOP SYSTEM FOR ALL PENETRATIONS INTO OR THROUGH ANY FIRE BARRIER
12/06/2005 SHEET ROCK NAILING Not ready for Inspection IVRS - Inspection :* NEED FRAMING APPROVAL BEFORE YOU PROCEED WITH DRYWALL.
12/06/2005 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999* NEED TO FIRE CAULK @ ALL PENETRATIONS @ FIRE WALLS W/INTUMESCENT U.L LISTED SYSTEM. PROVIDE SYSTEM.
APPRIVED @ 1015 ON 12/6/05. NOBODY ON SITE. LEFT REPORT ON PLANS. NO PERMIT IN SIGHT.