Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
Permit Number - T05CM04747
Inspection Description - SHEET ROCK NAILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2005 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
12/07/2005 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) I NEED CORRECTIONS NOTED 11/30/05 FOR FRAMING. PLUS THOSE NOTED BELOW 2) THE SHEET ROCK ABOVE 12' ON WEST WALL OF RATED CORRIDOR IS UNACCEPTABLE. FIRE BARRIERS REQUIRE TIGHT CONSTRUCTION ALL THE WAY TO DECK 3) PROVIDE A LISTED FIRE STOP SYSTEM FOR ALL PENETRATIONS INTO OR THROUGH ANY FIRE BARRIER |
|
12/06/2005 | SHEET ROCK NAILING | Not ready for Inspection | IVRS - Inspection :* NEED FRAMING APPROVAL BEFORE YOU PROCEED WITH DRYWALL. | |
12/06/2005 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED TO FIRE CAULK @ ALL PENETRATIONS @ FIRE WALLS W/INTUMESCENT U.L LISTED SYSTEM. PROVIDE SYSTEM. APPRIVED @ 1015 ON 12/6/05. NOBODY ON SITE. LEFT REPORT ON PLANS. NO PERMIT IN SIGHT. |