Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM04733
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/04/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. OPEN J-BOXES SOME HAVE NOT COMPLETE MAKE UP 2. SEISMIC TABS ON FIXTURES MUST BE SECURED ON ALL FOUR CORNERS - IF NOT USE SCREWS THREW GRID TO HOLD DOWN FIXTURES. 3. REMOVE CEILING TILES ON 2 ENDS OF 2X4 FIXTURES TO VIEW SEISMIC WIRES ON FIXTURES, SUPPORT FLEX LENGTHS EXCEEDING 6' LONG. 4. INSPECTOR NEEDS TO VERIFY SUPPORT OF CONDUITS RUN BEYOND CLASSROOMS, THIS PROJECT - HOME RUNS TO PANELS. |
|
05/10/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |