Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM04732
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2006 | FRAMING | Approved | IVRS - Inspection :* | |
01/03/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) SEE NOTES FROM 12/16: NEED A FINAL SPECIAL INSPECTION REPORT FOR 4 MISSING BOLTS 2) I HAVE SEEN THE SHOP DRAWINGS; NEED A COPY OF THE MILL CERTIFICATION (IE...AISL, L.A. CITY, CANADA ETC... FOR SHOP WELDS) |
|
12/16/2005 | FRAMING | Partial Approval | IVRS - Inspection :*PROVIDE SPECIAL INSP. REPORTS FOR HIGH STRENGTH BOLTING STEEL FABRICATOR CERTIFIED BY STATE OF CA AND CANADA MILL CERTS TO BE FAXED |