Permit: T05CM04729

Parcel: 133300510

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/07/2006 FRAMING Approved IVRS - Inspection :*
08/04/2006 FRAMING Partial Approval IVRS - Inspection :*
1) COMPLETE BLOCKING
2) NEED DWV TEST
07/31/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
NO ACCESS
DOGS IN YARD
07/24/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIREBLOCK BETWEEN FURRED TOP PLATES AND BLOCK
2) NEED OUTLET WITHIN 6' OF ENTRY DOOR
3) ADD OR EXPOSE LEDGER BOLTS WHERE NEEDED
4) NEED CONVENIENCE OUTLET ON WEST SIDE OF KITCHEN 1/2 WALL
5) NEED MASTER AT S. W. KITCHEN COUNTER AND UNDER EAST WINDOW
6) NEED DWV H20
7) BLOCK LAUNDRY DUCT BOOT
8) NAIL PROTECT DRYER VENT AND TPR PIPE
9) MOVE PEX 12" FROM CAN LIGHTS
10) NAIL PROTECT ABS WHERE NEEDED
11) RETURN DUCT BLOCKED IN HALL
12) SECURE MASTER SHOWER PLUMBING