Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 15 PSI TEST IS OK LEFT GAS CARD ALL CORRECTIONS HAVE BEEN MADE |
|
| 09/15/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 15 PSI TEST PROVIDE A 90 DEGREE ELBOW AT END OF T AND P RELIEF DRAIN LINE. WATER HEATER VENT CANNOT START WITH 4" VENT PIPE, THEN REDUCE TO 3". PROVIDE 3" THE ENTIRE LENGTH. SCREW THE VENT TO THE DRAFT DIVERTOR ON WATER HEATER. RELOCATE WATER HEATER VENT. VENT CANNOT TERMINATE WITHIN 10' OF ANY WINDOW, DOOR, OR BLDG. CONDENSATE CANNOT DRIP ONTO A HARD SURFACE. REMOVE THE PLUGGED TIE ON THE GAS LINE OR ROOF AND RETEST SYSTEM. |