Permit: T05CM04715

Parcel: 126122610


Addresses:

4669 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM04715

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL C OF O
01/10/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLEX DUCT AND FOIL BACK INSULATION INSIDE THE BLDG MUST BE MINIMUM R-5 AS PER 2000 I.E.C.C.
2) MARK THE UNIT DATA PLATE WITH PROPER HEAT KITCHEN INSTALLED AND FUSE ACCORDINGLY
3) CONDENSATE DRAIN CANNOT BE DBL TRAPPED
4) IDENTIFY CIRCUIT BREAKER FOR A/C UNIT
5) BREAKER MUST BE 25 AMP AS PER UNIT DATA PLATE
6) #12 WIRE MAY NOT BE ADEQUATE