Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM04715
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL C OF O |
|
| 01/10/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX DUCT AND FOIL BACK INSULATION INSIDE THE BLDG MUST BE MINIMUM R-5 AS PER 2000 I.E.C.C. 2) MARK THE UNIT DATA PLATE WITH PROPER HEAT KITCHEN INSTALLED AND FUSE ACCORDINGLY 3) CONDENSATE DRAIN CANNOT BE DBL TRAPPED 4) IDENTIFY CIRCUIT BREAKER FOR A/C UNIT 5) BREAKER MUST BE 25 AMP AS PER UNIT DATA PLATE 6) #12 WIRE MAY NOT BE ADEQUATE |