Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED. 2. CANNOT CHECK CONNECTIONS OF OFFICE FURNITURE. VISUAL APPEARS LOOSE FITTINGS. 3. AREA STILL OCCUPIED. 4. WHERE IS RECEPTACLE AS PER 210.63? 25' ON SAME LEVEL. 5. A/C DISCONNECTS NOT TO BE LOCATED ON PANELS THAT HAVE ACCESS 440.14 6. REPLACE MISSING PARTS FOR FLOOR BOXES |
|
| 01/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AREA OCCUPIED WITHOUT INSPECTION - UNABLE TO LOOK AT TERMINATIONS 1. FINISH CONNECTIONS TO FLOOR BOXES 2. VDV CABELING TO BE AS PER 725.2 &6, 800.2 & 6 3. PLANS NOT ON SITE |