Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM04715

Parcel: 126122610


Addresses:

4669 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM04715

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/29/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEIVED LETTER FOR M/C CABLE
OK STUDFRAME WALLS
12/28/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROTECT PVC CONDUITS AT BASE PLATE
2) PROTECT M/C CABLE AT SHALLOW STUDS AND SUPPORT AT 6' INTERVALS
3) PLEASE PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE. PLANS CALL FOR CONDUIT
4) WHERE IS DATA OUTLET IN ROOM 101