Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/29/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED LETTER FOR M/C CABLE OK STUDFRAME WALLS |
|
| 12/28/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROTECT PVC CONDUITS AT BASE PLATE 2) PROTECT M/C CABLE AT SHALLOW STUDS AND SUPPORT AT 6' INTERVALS 3) PLEASE PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE. PLANS CALL FOR CONDUIT 4) WHERE IS DATA OUTLET IN ROOM 101 |