Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/01/2005 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE #1-DBL WALL VENT PIPE NEEDS TO BE <1> ONE INCH FROM ALL WOOD, THIS NEEDS TO BE CUT 1" ALL THE WAY AROUND PASSING THRU ROOF SHEATHING 2) DO THIS SO YOU CAN SHEETROCK YOUR JOB |
|
| 10/27/2005 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*PROVIDE A MIN 1" CLEARANCE FROM COMBUSTIBLES AROUND WATER HEATER VENT. PROVIDE MIN 3 SCREWS IN ALL JOINTS & CONNECTIONS ON WATER HEATER VENT CONNECTOR. REMOVE FOIL TAPE FROM DOUBLE WALL VENT. STRAP BATHROOM EXHAUST DUCT TO ROOF JOIST-TAPE NOT HOLDING. CONDENSATE DRAINS ON ROOF CANNOT TERMINATE INTO SEWER VENTS. MUST GO TO AN APPROVED LOCATION. |
|
| 10/20/2005 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*PROVIDE A DOUBLE WALL VENT THRU ROOF FOR WATER HEATER. PROVIDE A BATHROOM EXHAUST FAN. |