Permit: T05CM04699

Parcel: 106030150

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05, 10, 36, 50, 85, 90
09/25/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN CLEARANCES AT SERVICE 110.26
2. SUPPORT CONDUIT & CAR FLEX FOR IRRIGATION
3. TIGHTEN LOOSE FITTINGS IRRIGATION & AC'S
4. ANTI-OXIDE COMPOUND ON ALL ALUMINUM CONDUCTORS
5. USE AN APPROVED CONNECTOR AT HOODS
6. USE SPLICE CONNECTORS FOR GROUNDS - LIGHT FIXTURES
7. COMPLETELY ID UNGROUNDED CONDUCTORS OF CABLES
8. PANEL SCHEDULES TO BE AS PER 408.4 -
NO ABBREVIATIONS