Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/20/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNIT 4 & UNIT 10: EXHAUST FAN T-TOP MISSING SCREEN 2) SOME CONDENSORS NOT LEVEL. NOT ON CURBS AS PER PLAN. PROVIDE SERVICE RECEPTS WITHIN 25' OF EQUIPMENT ON ROOF 3) PROVIDE VIBRATION ISOLATORS UNDER CONDENSORS AS PER PLAN 4) ALL GLUED CONDENSATE FITTINGS MUST FIRST BE PRIMERED 5) PROVIDE SECONDARY DRAINS 6) RETURN AIR NOT ADEQUATE |