Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TIGHTEN FLEX CONNECTORS 2. PLEASE PREVENT DIELECTRIC CONTACT 3. SAME SIZED GROUNDS UNDER TERMINAL SCREWS 4. MAINTAIN WORKING CLEARANCES IN FRONT OF OWNERS PANEL 5. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTABLE PRODUCT 6. MAINTAIN WORKING CLEARANCE AC #4 7. SUPPORT LIQUID TUFF UP OFF OF ROOF DID NOT INSPECT #10 OR 11 |
|
| 09/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION GO THROUGH ALL UNITS AND CHECK THAT ALL PREVIOUS (AND ANY OTHER) CORRECTIONS HAVE BEEN MADE - ALSO, PUT BLANKS IN OPEN BREAKER SPACES ALSO, 1. UNIT #10 AC NOT COLD? 2. NO DISCONNECT FOR AIR HANDLER 3. HAVE UNDERSIZED CKT TO AIR HANDLER - NEED MINIMUM 47 AMP CKT AMPACITY - YOU HAVE #10 ROMEX? CHECK SAME UNIT #11 |
|
| 09/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT #4 ONLY - CHECK OTHERS 1. STRAP A.H & WATER HEATER FLEX 2. INSTALL ALL BULBS 3. AC NOT WORKING 4. 2 NEUTRALS NOT ALLOWED UNDER SAME SCREW IN PANEL 5. ONLY SAME SIZE GROUNDS UNDER GROUND BAR SCREW 6. PANEL DIRECTORIES TO BE CORRECT ROOFTOP 7. STRAP FLEX WITHIN 12" OF TERMINATIONS 8. IDENTIFY DISCONNECTS WITH UNIT NUMBERS AT SERVICE 9. IDENTIFY ALL SERVICE DISCONNECTS 10. INSTALL ALL COVER SCREWS 11. SERVICE TO HAVE MINIMUM 36" IN FRONT CLEARANCE DISHWASHERS 1. NEED PROPER CONNECTOR FOR CORDS 2. MAX LENGTH FOR DISHWASHER CORD IS 48" 3. CORDS WIRED IMPROPERLY - HAVE REVERSE POLARITY ALSO, CHECK BOX FOR EXTENDERS AS NEEDED PARTIAL INSPECTION - GO THROUGH ALL UNITS SINCE YOU HAVE 4-WIRE RANGE CKT'S, BONDING STRAP BETWEEN NEUTRAL AND GROUND AT RANGE J-BOXES NEEDS TO BE REMOVED. |