Permit: T05CM04698

Parcel: 106030150

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. TIGHTEN FLEX CONNECTORS
2. PLEASE PREVENT DIELECTRIC CONTACT
3. SAME SIZED GROUNDS UNDER TERMINAL SCREWS
4. MAINTAIN WORKING CLEARANCES IN FRONT OF OWNERS PANEL
5. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTABLE PRODUCT
6. MAINTAIN WORKING CLEARANCE AC #4
7. SUPPORT LIQUID TUFF UP OFF OF ROOF

DID NOT INSPECT #10 OR 11
09/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION

GO THROUGH ALL UNITS AND CHECK THAT ALL PREVIOUS (AND ANY OTHER) CORRECTIONS HAVE BEEN MADE - ALSO, PUT BLANKS IN OPEN BREAKER SPACES

ALSO,
1. UNIT #10 AC NOT COLD?
2. NO DISCONNECT FOR AIR HANDLER
3. HAVE UNDERSIZED CKT TO AIR HANDLER - NEED
MINIMUM 47 AMP CKT AMPACITY - YOU HAVE #10 ROMEX?
CHECK SAME UNIT #11
09/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT #4 ONLY - CHECK OTHERS
1. STRAP A.H & WATER HEATER FLEX
2. INSTALL ALL BULBS
3. AC NOT WORKING
4. 2 NEUTRALS NOT ALLOWED UNDER SAME SCREW IN PANEL
5. ONLY SAME SIZE GROUNDS UNDER GROUND BAR SCREW
6. PANEL DIRECTORIES TO BE CORRECT

ROOFTOP
7. STRAP FLEX WITHIN 12" OF TERMINATIONS
8. IDENTIFY DISCONNECTS WITH UNIT NUMBERS

AT SERVICE
9. IDENTIFY ALL SERVICE DISCONNECTS
10. INSTALL ALL COVER SCREWS
11. SERVICE TO HAVE MINIMUM 36" IN FRONT CLEARANCE

DISHWASHERS
1. NEED PROPER CONNECTOR FOR CORDS
2. MAX LENGTH FOR DISHWASHER CORD IS 48"
3. CORDS WIRED IMPROPERLY - HAVE REVERSE POLARITY

ALSO, CHECK BOX FOR EXTENDERS AS NEEDED
PARTIAL INSPECTION - GO THROUGH ALL UNITS

SINCE YOU HAVE 4-WIRE RANGE CKT'S, BONDING STRAP BETWEEN NEUTRAL AND GROUND AT RANGE J-BOXES NEEDS TO BE REMOVED.